İçeriğe geç
Proxus 2.0.1 2.0 geçişinden sonra lisans ve giriş düzeltmeleri Sürüm notları

Schneider Electric iEM3000 Modbus register haritası

Diğer adları: Acti9 iEM3000 · iEM3150 · iEM3155 · iEM3250 · iEM3255 · iEM3350 · iEM3355 · iEM3455 · iEM3555 · A9MEM3150 · A9MEM3155 · A9MEM3250 · A9MEM3255 · A9MEM3350 · A9MEM3355 · A9MEM3455 · A9MEM3555

Schneider Electric iEM3000 için 98 Modbus register: hatta gönderilen adres, 30001 biçimindeki referans, veri tipi, byte sırası, birim ve ölçek. Kaynak: iEM3000 series user manual, Communications via Modbus (iEM3000 modbus register).

Acti9 iEM3000 DIN-rail energy meters with Modbus RTU (iEM3150 to iEM3555); measurements are 32-bit floats, energies also as 64-bit integers.

Cihaz tipi
Enerji sayacı
Register sayısı
98
Arayüzler
Modbus RTU
Byte sırası (çok register’lı değerler)
ABCD
Seri port ayarları
9600, 19200 or 38400 baud, even/odd/none parity, 1 stop bit (set on the display)
Kapsanan modeller
iEM3150, iEM3155, iEM3250, iEM3255, iEM3350, iEM3355, iEM3455, iEM3555

Cihazda doğrulama

Henüz cihazda doğrulanmadı. Harita üretici dokümanından aktarıldı ve bir betikle dokümana karşı kontrol edildi; ilk okumaları cihazın ekranıyla karşılaştırın.

Kendi cihazınızda doğrulayın Seviyeler ne anlama geliyor

Bağlantı notları

  • Every register here is a holding register (function code 3).
  • Addresses are the manual's register numbers minus one, the convention of the other PowerLogic maps here (the numbers match the PM5000 lists, e.g. Current I1 = 3000). The manual calls its numbers the address in the frame; if every read is off by one register, use the manual's number.
  • Word order is not stated in the manual; ABCD as for the PM5000 lists.
  • Settings marked in the notes are changed with setup commands written to register 5250 (function 16); the command interface registers are left out.
  • The per-phase reactive energy registers 45128-45132 of the manual's 1PH4W addendum are left out because their unit (kVARh) contradicts the other float energies (VARh).

Register’lar

Üretici dokümanındaki gruplara göre. Register adları kaynak dokümandaki gibi İngilizcedir.

Enerji 17 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Energy Reset Date and Timeenergy_reset_date_and_time 43252 0x0CB3 raw
Input Metering Accumulation Reset Date and Timeinput_metering_accumulation_reset_date_and_time 43554 0x0DE1 raw
MultiTariffs Energy Active Ratemultitariffs_energy_active_rate 44191 0x105E uint16
Total Active Energy Importtotal_active_energy_import 43204 0x0C83 int64 ABCD Wh
Total Active Energy Exporttotal_active_energy_export 43208 0x0C87 int64 ABCD Wh
Total Reactive Energy Importtotal_reactive_energy_import 43220 0x0C93 int64 ABCD VARh
Total Reactive Energy Exporttotal_reactive_energy_export 43224 0x0C97 int64 ABCD VARh
Partial Active Energy Importpartial_active_energy_import 43256 0x0CB7 int64 ABCD Wh
Partial Reactive Energy Importpartial_reactive_energy_import 43272 0x0CC7 int64 ABCD VARh
Active Energy Import Phase 1active_energy_import_phase_1 43518 0x0DBD int64 ABCD Wh
Active Energy Import Phase 2active_energy_import_phase_2 43522 0x0DC1 int64 ABCD Wh
Active Energy Import Phase 3active_energy_import_phase_3 43526 0x0DC5 int64 ABCD Wh
Input Metering Accumulationinput_metering_accumulation 43558 0x0DE5 int64 ABCD
Rate A Active Energy Importrate_a_active_energy_import 44196 0x1063 int64 ABCD Wh
Rate B Active Energy Importrate_b_active_energy_import 44200 0x1067 int64 ABCD Wh
Rate C Active Energy Importrate_c_active_energy_import 44204 0x106B int64 ABCD Wh
Rate D Active Energy Importrate_d_active_energy_import 44208 0x106F int64 ABCD Wh
System 8 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Meter Namemeter_name 40030 0x001D string
Meter Modelmeter_model 40050 0x0031 string
Manufacturermanufacturer 40070 0x0045 string
Serial Numberserial_number 40130 0x0081 uint32 ABCD
Date of Manufacturedate_of_manufacture 40132 0x0083 raw
Hardware Revisionhardware_revision 40136 0x0087 string
Present Firmware Versionpresent_firmware_version 41637 0x0664 uint16
Date/Timedate_time 41845 0x0734 raw
Meter setup 12 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Meter Operation Timermeter_operation_timer 42004 0x07D3 uint32 ABCD s
Number of Phasesnumber_of_phases 42014 0x07DD uint16
Number of Wiresnumber_of_wires 42015 0x07DE uint16
Power Systempower_system 42016 0x07DF uint16
Nominal Frequencynominal_frequency 42017 0x07E0 uint16 Hz
Number VTsnumber_vts 42025 0x07E8 uint16
VT Primaryvt_primary 42026 0x07E9 float32 ABCD V
VT Secondaryvt_secondary 42028 0x07EB uint16 V
Number CTsnumber_cts 42029 0x07EC uint16
CT Primaryct_primary 42030 0x07ED uint16 A
CT Secondaryct_secondary 42031 0x07EE uint16 A
VT Connection Typevt_connection_type 42036 0x07F3 uint16
Energy pulse output 3 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Energy Pulse Durationenergy_pulse_duration 42129 0x0850 uint16 ms
Digital Output Associationdigital_output_association 42131 0x0852 uint16
Pulse Weightpulse_weight 42132 0x0853 float32 ABCD pulse/kWh
Communications 4 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Protocolprotocol 46500 0x1963 uint16
Addressaddress 46501 0x1964 uint16
Baud Ratebaud_rate 46502 0x1965 uint16
Parityparity 46503 0x1966 uint16
Inputs outputs 6 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Input Metering Labelinput_metering_label 47032 0x1B77 string
Input Metering Pulse Constantinput_metering_pulse_constant 47052 0x1B8B float32 ABCD pulse/unit
Input Metering Digital Input Associationinput_metering_digital_input_association 47055 0x1B8E uint16
Digital Input Control Modedigital_input_control_mode 47274 0x1C69 uint16
Digital Input Statusdigital_input_status 48905 0x22C8 bitfield
Digital Output Control Mode Statusdigital_output_control_mode_status 49673 0x25C8 uint16
Meter data 24 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Current I1current_i1 43000 0x0BB7 float32 ABCD A
Current I2current_i2 43002 0x0BB9 float32 ABCD A
Current I3current_i3 43004 0x0BBB float32 ABCD A
Current Avgcurrent_avg 43010 0x0BC1 float32 ABCD A
Voltage L1-L2voltage_l1_l2 43020 0x0BCB float32 ABCD V
Voltage L2-L3voltage_l2_l3 43022 0x0BCD float32 ABCD V
Voltage L3-L1voltage_l3_l1 43024 0x0BCF float32 ABCD V
Voltage L-L Avgvoltage_l_l_avg 43026 0x0BD1 float32 ABCD V
Voltage L1-Nvoltage_l1_n 43028 0x0BD3 float32 ABCD V
Voltage L2-Nvoltage_l2_n 43030 0x0BD5 float32 ABCD V
Voltage L3-Nvoltage_l3_n 43032 0x0BD7 float32 ABCD V
Voltage L-N Avgvoltage_l_n_avg 43036 0x0BDB float32 ABCD V
Active Power Phase 1active_power_phase_1 43054 0x0BED float32 ABCD kW
Active Power Phase 2active_power_phase_2 43056 0x0BEF float32 ABCD kW
Active Power Phase 3active_power_phase_3 43058 0x0BF1 float32 ABCD kW
Total Active Powertotal_active_power 43060 0x0BF3 float32 ABCD kW
Total Reactive Powertotal_reactive_power 43068 0x0BFB float32 ABCD kVAR
Total Apparent Powertotal_apparent_power 43076 0x0C03 float32 ABCD kVA
Total Power Factortotal_power_factor 43084 0x0C0B float32 ABCD
Frequencyfrequency 43110 0x0C25 float32 ABCD Hz
Power Factor Total IECpower_factor_total_iec 43192 0x0C77 float32 ABCD
Power Factor Total Lead Lagpower_factor_total_lead_lag 43194 0x0C79 float32 ABCD
Power Factor Total IEC (UInt16)power_factor_total_iec_uint16 43196 0x0C7B uint16
Power Factor Total Lead Lag (UInt16)power_factor_total_lead_lag_uint16 43197 0x0C7C uint16
Energy float 14 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Total Active Energy Import (float)total_active_energy_import_float 445100 0xB02B float32 ABCD Wh
Total Active Energy Export (float)total_active_energy_export_float 445102 0xB02D float32 ABCD Wh
Total Reactive Energy Import (float)total_reactive_energy_import_float 445104 0xB02F float32 ABCD VARh
Total Reactive Energy Export (float)total_reactive_energy_export_float 445106 0xB031 float32 ABCD VARh
Partial Active Energy Import (float)partial_active_energy_import_float 445108 0xB033 float32 ABCD Wh
Partial Reactive Energy Import (float)partial_reactive_energy_import_float 445110 0xB035 float32 ABCD VARh
Active Energy Import Phase 1 (float)active_energy_import_phase_1_float 445112 0xB037 float32 ABCD Wh
Active Energy Import Phase 2 (float)active_energy_import_phase_2_float 445114 0xB039 float32 ABCD Wh
Active Energy Import Phase 3 (float)active_energy_import_phase_3_float 445116 0xB03B float32 ABCD Wh
Input Metering Accumulation (float)input_metering_accumulation_float 445118 0xB03D float32 ABCD
Rate A Active Energy Import (float)rate_a_active_energy_import_float 445120 0xB03F float32 ABCD Wh
Rate B Active Energy Import (float)rate_b_active_energy_import_float 445122 0xB041 float32 ABCD Wh
Rate C Active Energy Import (float)rate_c_active_energy_import_float 445124 0xB043 float32 ABCD Wh
Rate D Active Energy Import (float)rate_d_active_energy_import_float 445126 0xB045 float32 ABCD Wh
Overload alarm 7 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Overload Alarm Setupoverload_alarm_setup 445001 0xAFC8 bitfield16
Overload Alarm Pickup Setpointoverload_alarm_pickup_setpoint 445002 0xAFC9 float32 ABCD kW
Overload Alarm Digital Output Associationoverload_alarm_digital_output_association 445004 0xAFCB bitfield16
Overload Alarm Activated Statusoverload_alarm_activated_status 445005 0xAFCC bitfield16
Overload Alarm Unacknowledged Statusoverload_alarm_unacknowledged_status 445006 0xAFCD bitfield16
Overload Alarm Last Time Stampoverload_alarm_last_time_stamp 445007 0xAFCE raw
Overload Alarm Last Valueoverload_alarm_last_value 445011 0xAFD2 float32 ABCD kW
Phase names 3 register
Ad ve anahtar Referans Adres Tip Byte sırası Birim Ölçek
Phase 1 Namephase_1_name 457000 0xDEA7 string
Phase 2 Namephase_2_name 457005 0xDEAC string
Phase 3 Namephase_3_name 457010 0xDEB1 string

Kaynak dokümanlar

Bu haritayı GitHub’da inceleyin (YAML)

Adıyla okuyun

iEM3000 cihazını yapay zekâ asistanıyla okuyun

Proxus Industrial MCP Server bu haritayı içerir. Haritayı cihaza tanımlayın; Claude, Cursor ya da VS Code register’ları anahtarıyla, doğru veri tipi, byte sırası, ölçek ve birimle okur. Yalnızca okur.

Bu cihaz Modbus RTU konuşur: bir Modbus TCP ağ geçidi üzerinden bağlanın; ağ geçidinin adresini ve cihazın unit ID’sini kullanın.

proxus-mcp.json

{
  "devices": {
    "iem3000-1": {
      "protocol": "modbus-tcp",
      "host": "192.168.10.40",
      "unit_id": 1,
      "map": "schneider-electric/iem3000"
    }
  }
}

Asistanınıza sorun

iem3000-1 cihazından total_active_energy_import, total_active_energy_export, total_reactive_energy_import değerlerini oku.

Yaptığı araç çağrısı

read_named(device: "iem3000-1", keys: ["total_active_energy_import", "total_active_energy_export", "total_reactive_energy_import"])

Bu cihaz sizde mi? Haritayı doğrulayın.

Asistanınızdan verify_device_map çalıştırmasını isteyin. Her register’ı yalnızca okuyarak bir kez okur, değerlerin makul olup olmadığını kontrol eder ve iki değeri ekranla karşılaştırmanızı ister. Bir rapor ve doldurulmuş bir GitHub kaydı hazırlar, siz gönderirsiniz; adınız bu haritanın doğrulayanlar listesine eklenir.

Çok sayıda cihazdan mı veri topluyorsunuz?

Proxus, Modbus TCP ve RTU cihazlarını makinelerin yanında okur, geçmiş veriyi saklar ve değerleri panolara, veritabanlarına ve yapay zekâya aktarır.

Proxus’ta Modbus Endüstriyel bağlantı