Siemens PAC2200CLP Modbus register haritası
Diğer adları: SENTRON PAC2200CLP · 7KM2200-2EA00-1JB1 · 7KM2200-2EA40-1JB1
Siemens PAC2200CLP için 81 Modbus register: hatta gönderilen adres, 30001 biçimindeki referans, veri tipi, byte sırası, birim ve ölçek. Kaynak: SENTRON 7KM power monitoring device PAC2200CLP Equipment Manual (12/2022).
SENTRON PAC2200CLP power monitoring device with Modbus TCP; measurements are 32-bit floats, energy counters 64-bit floats.
- Cihaz tipi
- Enerji analizörü
- Register sayısı
- 81
- Arayüzler
- Modbus TCP
- Byte sırası (çok register’lı değerler)
- ABCD
Cihazda doğrulama
Henüz cihazda doğrulanmadı. Harita üretici dokümanından aktarıldı ve bir betikle dokümana karşı kontrol edildi; ilk okumaları cihazın ekranıyla karşılaştırın.
Bağlantı notları
- Addresses are the manual's offsets, sent unchanged, the convention of this repository's PAC3200 map; the manual has no example frame to settle it.
- Function code 3 or 4 reads the same registers; reading from the middle of a multi-register value is refused.
- Modbus TCP uses port 502 by default; the port is configurable.
Register’lar
Üretici dokümanındaki gruplara göre. Register adları kaynak dokümandaki gibi İngilizcedir.
Anlık değerler 30 register
| Ad ve anahtar | Referans | Adres | Tip | Byte sırası | Birim | Ölçek |
|---|---|---|---|---|---|---|
Voltage L1-Nvoltage_l1_n | 40002 | 0x0001 | float32 | ABCD | V | |
Voltage L2-Nvoltage_l2_n | 40004 | 0x0003 | float32 | ABCD | V | |
Voltage L3-Nvoltage_l3_n | 40006 | 0x0005 | float32 | ABCD | V | |
Voltage L1-L2voltage_l1_l2 | 40008 | 0x0007 | float32 | ABCD | V | |
Voltage L2-L3voltage_l2_l3 | 40010 | 0x0009 | float32 | ABCD | V | |
Voltage L3-L1voltage_l3_l1 | 40012 | 0x000B | float32 | ABCD | V | |
Current L1current_l1 | 40014 | 0x000D | float32 | ABCD | A | |
Current L2current_l2 | 40016 | 0x000F | float32 | ABCD | A | |
Current L3current_l3 | 40018 | 0x0011 | float32 | ABCD | A | |
Apparent power L1apparent_power_l1 | 40020 | 0x0013 | float32 | ABCD | VA | |
Apparent power L2apparent_power_l2 | 40022 | 0x0015 | float32 | ABCD | VA | |
Apparent power L3apparent_power_l3 | 40024 | 0x0017 | float32 | ABCD | VA | |
Active power L1active_power_l1 | 40026 | 0x0019 | float32 | ABCD | W | |
Active power L2active_power_l2 | 40028 | 0x001B | float32 | ABCD | W | |
Active power L3active_power_l3 | 40030 | 0x001D | float32 | ABCD | W | |
Reactive power L1reactive_power_l1 | 40032 | 0x001F | float32 | ABCD | var | |
Reactive power L2reactive_power_l2 | 40034 | 0x0021 | float32 | ABCD | var | |
Reactive power L3reactive_power_l3 | 40036 | 0x0023 | float32 | ABCD | var | |
Power factor L1power_factor_l1 | 40038 | 0x0025 | float32 | ABCD | ||
Power factor L2power_factor_l2 | 40040 | 0x0027 | float32 | ABCD | ||
Power factor L3power_factor_l3 | 40042 | 0x0029 | float32 | ABCD | ||
Frequencyfrequency | 40056 | 0x0037 | float32 | ABCD | Hz | |
Average voltage L-Naverage_voltage_l_n | 40058 | 0x0039 | float32 | ABCD | V | |
Average voltage L-Laverage_voltage_l_l | 40060 | 0x003B | float32 | ABCD | V | |
Average currentaverage_current | 40062 | 0x003D | float32 | ABCD | A | |
Total apparent powertotal_apparent_power | 40064 | 0x003F | float32 | ABCD | VA | |
Total active powertotal_active_power | 40066 | 0x0041 | float32 | ABCD | W | |
Total reactive powertotal_reactive_power | 40068 | 0x0043 | float32 | ABCD | var | |
Total power factortotal_power_factor | 40070 | 0x0045 | float32 | ABCD | ||
Neutral current (calculated)current_n | 40072 | 0x0047 | float32 | ABCD | A |
Enerji 14 register
| Ad ve anahtar | Referans | Adres | Tip | Byte sırası | Birim | Ölçek |
|---|---|---|---|---|---|---|
Active energy import, tariff 1active_import_energy_t1 | 40802 | 0x0321 | float64 | ABCD | Wh | |
Active energy import, tariff 2active_import_energy_t2 | 40806 | 0x0325 | float64 | ABCD | Wh | |
Active energy export, tariff 1active_export_energy_t1 | 40810 | 0x0329 | float64 | ABCD | Wh | |
Active energy export, tariff 2active_export_energy_t2 | 40814 | 0x032D | float64 | ABCD | Wh | |
Reactive energy import, tariff 1reactive_import_energy_t1 | 40818 | 0x0331 | float64 | ABCD | varh | |
Reactive energy import, tariff 2reactive_import_energy_t2 | 40822 | 0x0335 | float64 | ABCD | varh | |
Reactive energy export, tariff 1reactive_export_energy_t1 | 40826 | 0x0339 | float64 | ABCD | varh | |
Reactive energy export, tariff 2reactive_export_energy_t2 | 40830 | 0x033D | float64 | ABCD | varh | |
Apparent energy, tariff 1apparent_energy_t1 | 40834 | 0x0341 | float64 | ABCD | VAh | |
Apparent energy, tariff 2apparent_energy_t2 | 40838 | 0x0345 | float64 | ABCD | VAh | |
Secondary total active energy import (MID register)mid_secondary_active_import | 40962 | 0x03C1 | float64 | ABCD | Wh | |
Secondary total active energy export (MID register)mid_secondary_active_export | 40966 | 0x03C5 | float64 | ABCD | Wh | |
Total active energy import (MID register)mid_total_active_import | 40970 | 0x03C9 | float64 | ABCD | Wh | |
Total active energy export (MID register)mid_total_active_export | 40974 | 0x03CD | float64 | ABCD | Wh |
Faz enerjileri 30 register
| Ad ve anahtar | Referans | Adres | Tip | Byte sırası | Birim | Ölçek |
|---|---|---|---|---|---|---|
L1 active energy import, tariff 1l1_active_import_energy_t1 | 40842 | 0x0349 | float64 | ABCD | Wh | |
L1 active energy import, tariff 2l1_active_import_energy_t2 | 40846 | 0x034D | float64 | ABCD | Wh | |
L1 active energy export, tariff 1l1_active_export_energy_t1 | 40850 | 0x0351 | float64 | ABCD | Wh | |
L1 active energy export, tariff 2l1_active_export_energy_t2 | 40854 | 0x0355 | float64 | ABCD | Wh | |
L1 reactive energy import, tariff 1l1_reactive_import_energy_t1 | 40858 | 0x0359 | float64 | ABCD | varh | |
L1 reactive energy import, tariff 2l1_reactive_import_energy_t2 | 40862 | 0x035D | float64 | ABCD | varh | |
L1 reactive energy export, tariff 1l1_reactive_export_energy_t1 | 40866 | 0x0361 | float64 | ABCD | varh | |
L1 reactive energy export, tariff 2l1_reactive_export_energy_t2 | 40870 | 0x0365 | float64 | ABCD | varh | |
L1 apparent energy, tariff 1l1_apparent_energy_t1 | 40874 | 0x0369 | float64 | ABCD | VAh | |
L1 apparent energy, tariff 2l1_apparent_energy_t2 | 40878 | 0x036D | float64 | ABCD | VAh | |
L2 active energy import, tariff 1l2_active_import_energy_t1 | 40882 | 0x0371 | float64 | ABCD | Wh | |
L2 active energy import, tariff 2l2_active_import_energy_t2 | 40886 | 0x0375 | float64 | ABCD | Wh | |
L2 active energy export, tariff 1l2_active_export_energy_t1 | 40890 | 0x0379 | float64 | ABCD | Wh | |
L2 active energy export, tariff 2l2_active_export_energy_t2 | 40894 | 0x037D | float64 | ABCD | Wh | |
L2 reactive energy import, tariff 1l2_reactive_import_energy_t1 | 40898 | 0x0381 | float64 | ABCD | varh | |
L2 reactive energy import, tariff 2l2_reactive_import_energy_t2 | 40902 | 0x0385 | float64 | ABCD | varh | |
L2 reactive energy export, tariff 1l2_reactive_export_energy_t1 | 40906 | 0x0389 | float64 | ABCD | varh | |
L2 reactive energy export, tariff 2l2_reactive_export_energy_t2 | 40910 | 0x038D | float64 | ABCD | varh | |
L2 apparent energy, tariff 1l2_apparent_energy_t1 | 40914 | 0x0391 | float64 | ABCD | VAh | |
L2 apparent energy, tariff 2l2_apparent_energy_t2 | 40918 | 0x0395 | float64 | ABCD | VAh | |
L3 active energy import, tariff 1l3_active_import_energy_t1 | 40922 | 0x0399 | float64 | ABCD | Wh | |
L3 active energy import, tariff 2l3_active_import_energy_t2 | 40926 | 0x039D | float64 | ABCD | Wh | |
L3 active energy export, tariff 1l3_active_export_energy_t1 | 40930 | 0x03A1 | float64 | ABCD | Wh | |
L3 active energy export, tariff 2l3_active_export_energy_t2 | 40934 | 0x03A5 | float64 | ABCD | Wh | |
L3 reactive energy import, tariff 1l3_reactive_import_energy_t1 | 40938 | 0x03A9 | float64 | ABCD | varh | |
L3 reactive energy import, tariff 2l3_reactive_import_energy_t2 | 40942 | 0x03AD | float64 | ABCD | varh | |
L3 reactive energy export, tariff 1l3_reactive_export_energy_t1 | 40946 | 0x03B1 | float64 | ABCD | varh | |
L3 reactive energy export, tariff 2l3_reactive_export_energy_t2 | 40950 | 0x03B5 | float64 | ABCD | varh | |
L3 apparent energy, tariff 1l3_apparent_energy_t1 | 40954 | 0x03B9 | float64 | ABCD | VAh | |
L3 apparent energy, tariff 2l3_apparent_energy_t2 | 40958 | 0x03BD | float64 | ABCD | VAh |
Durum 4 register
| Ad ve anahtar | Referans | Adres | Tip | Byte sırası | Birim | Ölçek |
|---|---|---|---|---|---|---|
Device diagnostics and device statusdevice_status | 40206 | 0x00CD | bitfield | |||
Digital outputs statusdigital_outputs_status | 40208 | 0x00CF | bitfield | |||
Digital inputs statusdigital_inputs_status | 40210 | 0x00D1 | bitfield | |||
Active tariffactive_tariff | 40212 | 0x00D3 | uint32 | ABCD |
Counters 3 register
| Ad ve anahtar | Referans | Adres | Tip | Byte sırası | Birim | Ölçek |
|---|---|---|---|---|---|---|
Universal counteruniversal_counter | 40216 | 0x00D7 | uint32 | ABCD | ||
Relevant parameter changes counterparameter_changes_relevant | 40218 | 0x00D9 | uint32 | ABCD | ||
Counter all parameter changesparameter_changes_all | 40220 | 0x00DB | uint32 | ABCD |
Kaynak dokümanlar
- SENTRON 7KM power monitoring device PAC2200CLP Equipment Manual , Siemens, L1V30820585B-04, 12/2022 (erişim 2026-11-09) Appendix A.1.3, Modbus measured variables with the function codes 0x03 and 0x04.
Adıyla okuyun
PAC2200CLP cihazını yapay zekâ asistanıyla okuyun
Proxus Industrial MCP Server bu haritayı içerir. Haritayı cihaza tanımlayın; Claude, Cursor ya da VS Code register’ları anahtarıyla, doğru veri tipi, byte sırası, ölçek ve birimle okur. Yalnızca okur.
proxus-mcp.json
{
"devices": {
"pac2200clp-1": {
"protocol": "modbus-tcp",
"host": "192.168.10.40",
"unit_id": 1,
"map": "siemens/pac2200clp"
}
}
} Asistanınıza sorun
pac2200clp-1 cihazından voltage_l1_n, voltage_l2_n, voltage_l3_n değerlerini oku.
Yaptığı araç çağrısı
read_named(device: "pac2200clp-1", keys: ["voltage_l1_n", "voltage_l2_n", "voltage_l3_n"]) Bu cihaz sizde mi? Haritayı doğrulayın.
Asistanınızdan verify_device_map çalıştırmasını isteyin. Her register’ı yalnızca okuyarak bir kez okur, değerlerin makul olup olmadığını kontrol eder ve iki değeri ekranla karşılaştırmanızı ister. Bir rapor ve doldurulmuş bir GitHub kaydı hazırlar, siz gönderirsiniz; adınız bu haritanın doğrulayanlar listesine eklenir.
Çok sayıda cihazdan mı veri topluyorsunuz?
Proxus, Modbus TCP ve RTU cihazlarını makinelerin yanında okur, geçmiş veriyi saklar ve değerleri panolara, veritabanlarına ve yapay zekâya aktarır.