Proxus connects to LS Electric (formerly LSIS) XGT series PLCs using the FEnet (Fast Ethernet) or Cnet protocols.
Supported Protocols
| Protocol Type | Series | Connection | Port | Description |
|---|---|---|---|---|
LSIS_XGBFastEnet | XGB | Ethernet | 2004 | XGB Native Ethernet |
LSIS_XGKFastEnet | XGK | Ethernet | 2004 | XGK Native Ethernet |
LSIS_XGBCnet_OverTcp | XGB | Serial/Ethernet | - | Cnet over TCP |
Connection Parameters
| Parameter | Type | Required | Default | Description |
|---|---|---|---|---|
| Host | string | Yes | - | PLC IP Address |
| Port | int | No | 2004 | Default FEnet Port |
| BaseNo | byte | No | 0 | Rack/Base Number |
| SlotNo | byte | No | 1 | CPU Slot Number |
| CompanyId | string | No | LSIS-XGT | Protocol Identifier |
Address Syntax
LSIS uses specific prefixes for inputs, outputs, and memory.
| Area | Prefix | Description | Example |
|---|---|---|---|
| Input/Output | P | I/O Area | P0, P10 |
| Internal Relay | M | Internal Bit | M100, M0 |
| Data Register | D | Word Data | D100, D200 |
| Keep Relay | K | Retentive Bit | K0 |
| Timer | T | Timer | T0 |
| Counter | C | Counter | C0 |
info
Slot Configuration
Ensure BaseNo and SlotNo match the physical location of the Ethernet module or CPU in the rack.
Troubleshooting
lightbulb
Need Help?
For LSIS-specific error codes, see LSIS Error Codes. For general connectivity issues, see Gateway Issues.
Official Resources
- LS Electric: Download Center