Klemsan KLEA 320P Modbus register map
Also searched as: KLEA · KLEA Energy Analyzer · 606100
48 Modbus registers of the Klemsan KLEA 320P, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from KLEA Energy Analyzer User Manual (2022-08-24).
KLEA 320P network energy analyzer with RS485 Modbus RTU; measurements are 32-bit floats in holding registers.
- Device type
- Power analyser
- Registers
- 48
- Interfaces
- Modbus RTU
- Byte order (multi-register values)
- ABCD
Hardware verification
Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.
Connection notes
- Read with function 03; the manual's example frame reads address 0x0000, count 2, and decodes 43 5D 36 E0 as 221.2143555 V (big-endian float).
- Every value spans two registers; read them in pairs.
- Tariff indexes are also available as 64-bit floats from register 1366 onward; only the 32-bit copies are listed here.
Registers
Grouped as in the vendor document.
Voltage 8 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Average voltage of three phasesvoltage_avg_ln | 40001 | 0x0000 | float32 | ABCD | V | |
Voltage V1-2voltage_l1_l2 | 40015 | 0x000E | float32 | ABCD | V | |
Voltage V2-3voltage_l2_l3 | 40017 | 0x0010 | float32 | ABCD | V | |
Voltage V3-1voltage_l3_l1 | 40019 | 0x0012 | float32 | ABCD | V | |
Average line to line voltagevoltage_avg_ll | 40021 | 0x0014 | float32 | ABCD | V | |
Phase 1 voltagevoltage_l1_n | 40029 | 0x001C | float32 | ABCD | V | |
Phase 2 voltagevoltage_l2_n | 40153 | 0x0098 | float32 | ABCD | V | |
Phase 3 voltagevoltage_l3_n | 40277 | 0x0114 | float32 | ABCD | V |
Current 5 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Total current of three phasescurrent_total | 40003 | 0x0002 | float32 | ABCD | A | |
Neutral currentcurrent_neutral | 40023 | 0x0016 | float32 | ABCD | A | |
Phase 1 currentcurrent_l1 | 40031 | 0x001E | float32 | ABCD | A | |
Phase 2 currentcurrent_l2 | 40155 | 0x009A | float32 | ABCD | A | |
Phase 3 currentcurrent_l3 | 40279 | 0x0116 | float32 | ABCD | A |
Power 12 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Total active poweractive_power_total | 40005 | 0x0004 | float32 | ABCD | W | |
Total reactive powerreactive_power_total | 40007 | 0x0006 | float32 | ABCD | var | |
Total apparent powerapparent_power_total | 40009 | 0x0008 | float32 | ABCD | VA | |
Phase 1 active poweractive_power_l1 | 40033 | 0x0020 | float32 | ABCD | W | |
Phase 1 reactive powerreactive_power_l1 | 40035 | 0x0022 | float32 | ABCD | var | |
Phase 1 apparent powerapparent_power_l1 | 40037 | 0x0024 | float32 | ABCD | VA | |
Phase 2 active poweractive_power_l2 | 40157 | 0x009C | float32 | ABCD | W | |
Phase 2 reactive powerreactive_power_l2 | 40159 | 0x009E | float32 | ABCD | var | |
Phase 2 apparent powerapparent_power_l2 | 40161 | 0x00A0 | float32 | ABCD | VA | |
Phase 3 active poweractive_power_l3 | 40281 | 0x0118 | float32 | ABCD | W | |
Phase 3 reactive powerreactive_power_l3 | 40283 | 0x011A | float32 | ABCD | var | |
Phase 3 apparent powerapparent_power_l3 | 40285 | 0x011C | float32 | ABCD | VA |
Frequency 3 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Phase 1 frequencyfrequency_l1 | 40043 | 0x002A | float32 | ABCD | Hz | |
Phase 2 frequencyfrequency_l2 | 40167 | 0x00A6 | float32 | ABCD | Hz | |
Phase 3 frequencyfrequency_l3 | 40291 | 0x0122 | float32 | ABCD | Hz |
Energy 4 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Tariff 1 import active indext1_import_active_energy | 40405 | 0x0194 | float32 | ABCD | kWh | |
Tariff 1 export active indext1_export_active_energy | 40419 | 0x01A2 | float32 | ABCD | kWh | |
Tariff 1 import reactive indext1_import_reactive_energy | 40433 | 0x01B0 | float32 | ABCD | kvarh | |
Tariff 1 export reactive indext1_export_reactive_energy | 40447 | 0x01BE | float32 | ABCD | kvarh |
Power factor 8 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Average cos phi of three phasescos_phi_avg | 40011 | 0x000A | float32 | ABCD | ||
Average power factor of three phasespower_factor_avg | 40013 | 0x000C | float32 | ABCD | ||
Phase 1 cos phicos_phi_l1 | 40039 | 0x0026 | float32 | ABCD | ||
Phase 1 power factorpower_factor_l1 | 40041 | 0x0028 | float32 | ABCD | ||
Phase 2 cos phicos_phi_l2 | 40163 | 0x00A2 | float32 | ABCD | ||
Phase 2 power factorpower_factor_l2 | 40165 | 0x00A4 | float32 | ABCD | ||
Phase 3 cos phicos_phi_l3 | 40287 | 0x011E | float32 | ABCD | ||
Phase 3 power factorpower_factor_l3 | 40289 | 0x0120 | float32 | ABCD |
Quality 8 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Total voltage harmonic distortionthd_voltage_total | 40025 | 0x0018 | float32 | ABCD | % | |
Total current harmonic distortionthd_current_total | 40027 | 0x001A | float32 | ABCD | % | |
Phase 1 voltage THDthd_voltage_l1 | 40045 | 0x002C | float32 | ABCD | % | |
Phase 1 current THDthd_current_l1 | 40047 | 0x002E | float32 | ABCD | % | |
Phase 2 voltage THDthd_voltage_l2 | 40169 | 0x00A8 | float32 | ABCD | % | |
Phase 2 current THDthd_current_l2 | 40171 | 0x00AA | float32 | ABCD | % | |
Phase 3 voltage THDthd_voltage_l3 | 40293 | 0x0124 | float32 | ABCD | % | |
Phase 3 current THDthd_current_l3 | 40295 | 0x0126 | float32 | ABCD | % |
Source documents
- KLEA Energy Analyzer User Manual , Klemsan, 2022-08-24 (accessed 2026-11-09) Section 4, Table 4-4 Read-only Data. Linked from the KLEA 320P (606100) product page.
Read it by name
Read the KLEA 320P with an AI assistant
The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.
This device speaks Modbus RTU: reach it through a Modbus TCP gateway and use the gateway’s address with the device’s unit ID.
proxus-mcp.json
{
"devices": {
"klea-1": {
"protocol": "modbus-tcp",
"host": "192.168.10.40",
"unit_id": 1,
"map": "klemsan/klea-320p"
}
}
} Ask your assistant
Read voltage_avg_ln, voltage_l1_l2, voltage_l2_l3 from klea-1.
The tool call it makes
read_named(device: "klea-1", keys: ["voltage_avg_ln", "voltage_l1_l2", "voltage_l2_l3"]) Have this device? Verify the map.