SMA Sunny Tripower Smart Energy Modbus register map

Also searched as: STP5.0-3SE-40 · STP6.0-3SE-40 · STP8.0-3SE-40 · STP10.0-3SE-40 · STPxx-3SE-40

31 Modbus registers of the SMA Sunny Tripower Smart Energy, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from Parameters and Measured Values STP5.0-3SE-40 / STP6.0-3SE-40 / STP8.0-3SE-40 / STP10.0-3SE-40 (PARAMETER-HTML_STPxx-3SE-40_30109R_V11.zip) (V11, firmware 3.01.09.R).

SMA Sunny Tripower Smart Energy hybrid inverters through the SMA Modbus profile over Modbus TCP.

Device type
Solar inverter
Registers
31
Interfaces
Modbus TCP
Default unit ID
3
Byte order (multi-register values)
ABCD

Hardware verification

Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.

Verify it on your device What the levels mean

Connection notes

  • SMA Modbus register addresses are sent unchanged (only SunSpec addresses are reduced by 1). Read with function 03 or 04.
  • Enable the Modbus server in the inverter first. Values are big-endian, high word first; read each value as one block.
  • FIXn formats are given as scale (FIX2 = 0.01). The parameter list names no units for most values, so units are left out except for energy.
  • NaN is 0x80000000 for S32, 0xFFFFFFFF for U32 (0xFFFFFD for status values) and 0xFFFFFFFFFFFFFFFF for U64.
  • Writable registers are stored in flash; do not write them cyclically.

Registers

Grouped as in the vendor document.

Energy 1 registers
Name and key Reference Address Type Byte order Unit Scale
Total yieldtotal_yield 430514 0x7731 uint64 ABCD Wh
Status 4 registers
Name and key Reference Address Type Byte order Unit Scale
Conditioncondition 430202 0x75F9 uint32 ABCD
Grid relay statusgrid_relay_status 430218 0x7609 uint32 ABCD
Operating statusoperating_status 433004 0x80EB uint32 ABCD
General operating statusgeneral_operating_status 440030 0x9C5D uint32 ABCD
Ac 18 registers
Name and key Reference Address Type Byte order Unit Scale
Poweractive_power 430776 0x7837 int32 ABCD
Active power phase L1active_power_l1 430778 0x7839 int32 ABCD
Active power phase L2active_power_l2 430780 0x783B int32 ABCD
Active power phase L3active_power_l3 430782 0x783D int32 ABCD
Grid voltage phase L1voltage_l1_n 430784 0x783F uint32 ABCD × 0.01
Grid voltage phase L2voltage_l2_n 430786 0x7841 uint32 ABCD × 0.01
Grid voltage phase L3voltage_l3_n 430788 0x7843 uint32 ABCD × 0.01
Grid voltage phase L1 against L2voltage_l1_l2 430790 0x7845 uint32 ABCD × 0.01
Grid voltage phase L2 against L3voltage_l2_l3 430792 0x7847 uint32 ABCD × 0.01
Grid voltage phase L3 against L1voltage_l3_l1 430794 0x7849 uint32 ABCD × 0.01
Phase total currentcurrent_total 430796 0x784B uint32 ABCD × 0.001
Grid current phase L1current_l1 430978 0x7901 int32 ABCD × 0.001
Grid current phase L2current_l2 430980 0x7903 int32 ABCD × 0.001
Grid current phase L3current_l3 430982 0x7905 int32 ABCD × 0.001
Grid frequencyfrequency 430804 0x7853 uint32 ABCD × 0.01
Reactive powerreactive_power 431498 0x7B09 int32 ABCD
Apparent powerapparent_power 430814 0x785D int32 ABCD
Displacement power factordisplacement_power_factor 430950 0x78E5 uint32 ABCD × 0.001
Dc 1 registers
Name and key Reference Address Type Byte order Unit Scale
Insulation resistanceinsulation_resistance 430226 0x7611 uint32 ABCD
Battery 6 registers
Name and key Reference Address Type Byte order Unit Scale
Current battery state of chargebattery_soc 430846 0x787D uint32 ABCD
Battery currentbattery_current 430844 0x787B int32 ABCD × 0.001
Battery voltagebattery_voltage 430852 0x7883 uint32 ABCD × 0.01
Battery general operating statusbattery_operating_status 430956 0x78EB uint32 ABCD
Present battery chargebattery_charge_present 431394 0x7AA1 uint32 ABCD
Present battery dischargebattery_discharge_present 431396 0x7AA3 uint32 ABCD
Control 1 registers
Name and key Reference Address Type Byte order Unit Scale
General operating modeoperating_mode 440010 0x9C49 uint32 ABCD

Source documents

View this map on GitHub (YAML)

Read it by name

Read the Sunny Tripower Smart Energy with an AI assistant

The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.

proxus-mcp.json

{
  "devices": {
    "sunny-1": {
      "protocol": "modbus-tcp",
      "host": "192.168.10.40",
      "unit_id": 3,
      "map": "sma/sunny-tripower-smart-energy"
    }
  }
}

Ask your assistant

Read total_yield from sunny-1.

The tool call it makes

read_named(device: "sunny-1", keys: ["total_yield"])

Have this device? Verify the map.

Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.

Collecting from many devices?

Proxus reads Modbus TCP and RTU devices next to the machines, keeps the history and delivers the values to dashboards, databases and AI.

Modbus in Proxus Industrial connectivity