Skip to content
Proxus 2.0.1 Licence and sign-in fixes after the 2.0 upgrade Release notes

Lovato Electric DMG110 Modbus register map

Also searched as: DMG 110

55 Modbus registers of the Lovato Electric DMG110, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from DMG series digital multimeters-analyzers: Modbus communication protocol (07/02/2022).

Lovato DMG110 modular multimeter with built-in RS485; scaled 32-bit integers, 64-bit energy counters.

Device type
Power analyser
Registers
55
Interfaces
Modbus RTU, ASCII
Default unit ID
1
Byte order (multi-register values)
ABCD
Serial settings
9600 baud, 8 data bits, no parity, 1 stop bit
Registers per read
64

Hardware verification

Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.

Verify it on your device What the levels mean

Connection notes

  • Addresses here are the table addresses minus one, as the protocol document requires (its example reads L2 active power, table address 0016H, with start address 0015H).
  • Function 03 or 04 reads the measurements; 32-bit values are sent high word first, as the document's example response shows (00 01 FB 00 = 129792).
  • Energy counters at 1B20H and up are 4-word counters; the document marks them with software revision 07 in the DMG110/210 column and says earlier revisions roll over like the 2-word counters (at 19,999,999.99 kWh).
  • Frequency is in Hz/1000 on the DMG110 (Hz/100 only on the DMG210).

Registers

Grouped as in the vendor document.

Voltage 8 registers
Name and key Reference Address Type Byte order Unit Scale
L1 Phase Voltagevoltage_l1_n 30002 0x0001 uint32 ABCD V × 0.01
L2 Phase Voltagevoltage_l2_n 30004 0x0003 uint32 ABCD V × 0.01
L3 Phase Voltagevoltage_l3_n 30006 0x0005 uint32 ABCD V × 0.01
L1-L2 Voltagevoltage_l1_l2 30014 0x000D uint32 ABCD V × 0.01
L2-L3 Voltagevoltage_l2_l3 30016 0x000F uint32 ABCD V × 0.01
L3-L1 Voltagevoltage_l3_l1 30018 0x0011 uint32 ABCD V × 0.01
Eqv. Phase Voltagevoltage_phase_equivalent 30052 0x0033 uint32 ABCD V × 0.01
Eqv. Phase-To-Phase Voltagevoltage_phase_to_phase_equivalent 30054 0x0035 uint32 ABCD V × 0.01
Current 5 registers
Name and key Reference Address Type Byte order Unit Scale
L1 Currentcurrent_l1 30008 0x0007 uint32 ABCD A × 0.0001
L2 Currentcurrent_l2 30010 0x0009 uint32 ABCD A × 0.0001
L3 Currentcurrent_l3 30012 0x000B uint32 ABCD A × 0.0001
Eqv. Currentcurrent_equivalent 30056 0x0037 uint32 ABCD A × 0.0001
Neutral Currentcurrent_n 30072 0x0047 uint32 ABCD A × 0.0001
Power 12 registers
Name and key Reference Address Type Byte order Unit Scale
L1 Active Poweractive_power_l1 30020 0x0013 int32 ABCD W × 0.01
L2 Active Poweractive_power_l2 30022 0x0015 int32 ABCD W × 0.01
L3 Active Poweractive_power_l3 30024 0x0017 int32 ABCD W × 0.01
L1 Reactive Powerreactive_power_l1 30026 0x0019 int32 ABCD var × 0.01
L2 Reactive Powerreactive_power_l2 30028 0x001B int32 ABCD var × 0.01
L3 Reactive Powerreactive_power_l3 30030 0x001D int32 ABCD var × 0.01
L1 Apparent Powerapparent_power_l1 30032 0x001F uint32 ABCD VA × 0.01
L2 Apparent Powerapparent_power_l2 30034 0x0021 uint32 ABCD VA × 0.01
L3 Apparent Powerapparent_power_l3 30036 0x0023 uint32 ABCD VA × 0.01
Eqv. Active Poweractive_power_equivalent 30058 0x0039 int32 ABCD W × 0.01
Eqv. Reactive Powerreactive_power_equivalent 30060 0x003B int32 ABCD var × 0.01
Eqv. Apparent Powerapparent_power_equivalent 30062 0x003D uint32 ABCD VA × 0.01
Frequency 1 registers
Name and key Reference Address Type Byte order Unit Scale
Frequencyfrequency 30050 0x0031 uint32 ABCD Hz × 0.001
Energy 10 registers
Name and key Reference Address Type Byte order Unit Scale
Total imp. Active Energyactive_energy_imported_total 36944 0x1B1F uint64 ABCD kWh × 0.01
Total exported Active Energyactive_energy_exported_total 36948 0x1B23 uint64 ABCD kWh × 0.01
Total imp. Reactive Energyreactive_energy_imported_total 36952 0x1B27 uint64 ABCD kvarh × 0.01
Total exp. Reactive Energyreactive_energy_exported_total 36956 0x1B2B uint64 ABCD kvarh × 0.01
Total Apparent Energyapparent_energy_total 36960 0x1B2F uint64 ABCD kVAh × 0.01
Partial imp. Active Energyactive_energy_imported_partial 36964 0x1B33 uint64 ABCD kWh × 0.01
Partial exp. Active Energyactive_energy_exported_partial 36968 0x1B37 uint64 ABCD kWh × 0.01
Partial imp. Reactive Energyreactive_energy_imported_partial 36972 0x1B3B uint64 ABCD kvarh × 0.01
Partial exp Reactive Energyreactive_energy_exported_partial 36976 0x1B3F uint64 ABCD kvarh × 0.01
Partial Apparent Energyapparent_energy_partial 36980 0x1B43 uint64 ABCD kVAh × 0.01
Status 1 registers
Name and key Reference Address Type Byte order Unit Scale
Phase sequencephase_sequence 38432 0x20EF uint16
Power factor 4 registers
Name and key Reference Address Type Byte order Unit Scale
L1 Power Factorpower_factor_l1 30038 0x0025 int32 ABCD × 0.0001
L2 Power Factorpower_factor_l2 30040 0x0027 int32 ABCD × 0.0001
L3 Power Factorpower_factor_l3 30042 0x0029 int32 ABCD × 0.0001
Eqv Power Factorpower_factor_equivalent 30064 0x003F int32 ABCD × 0.0001
Quality 3 registers
Name and key Reference Address Type Byte order Unit Scale
Phase-Phase Voltage Asymmetryvoltage_asymmetry_phase_phase 30066 0x0041 uint32 ABCD % × 0.01
Phase-Neutral Voltage Asymmetryvoltage_asymmetry_phase_neutral 30068 0x0043 uint32 ABCD % × 0.01
Current Asymmetrycurrent_asymmetry 30070 0x0045 uint32 ABCD % × 0.01
Harmonics 9 registers
Name and key Reference Address Type Byte order Unit Scale
L1 Voltage Thdthd_voltage_l1 30084 0x0053 uint32 ABCD % × 0.01
L2 Voltage Thdthd_voltage_l2 30086 0x0055 uint32 ABCD % × 0.01
L3 Voltage Thdthd_voltage_l3 30088 0x0057 uint32 ABCD % × 0.01
L1 Current Thdthd_current_l1 30090 0x0059 uint32 ABCD % × 0.01
L2 Current Thdthd_current_l2 30092 0x005B uint32 ABCD % × 0.01
L3 Current Thdthd_current_l3 30094 0x005D uint32 ABCD % × 0.01
L1-2 Voltage Thdthd_voltage_l1_l2 30096 0x005F uint32 ABCD % × 0.01
L2-3 Voltage Thdthd_voltage_l2_l3 30098 0x0061 uint32 ABCD % × 0.01
L3-1 Voltage Thdthd_voltage_l3_l1 30100 0x0063 uint32 ABCD % × 0.01
Counters 2 registers
Name and key Reference Address Type Byte order Unit Scale
Total Hour meterhour_meter_total 37680 0x1DFF uint32 ABCD s
Partial Hour meterhour_meter_partial 37682 0x1E01 uint32 ABCD s

Source documents

View this map on GitHub (YAML)

Read it by name

Read the DMG110 with an AI assistant

The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.

This device speaks Modbus RTU: reach it through a Modbus TCP gateway and use the gateway’s address with the device’s unit ID.

proxus-mcp.json

{
  "devices": {
    "dmg110-1": {
      "protocol": "modbus-tcp",
      "host": "192.168.10.40",
      "unit_id": 1,
      "map": "lovato-electric/dmg110"
    }
  }
}

Ask your assistant

Read voltage_l1_n, voltage_l2_n, voltage_l3_n from dmg110-1.

The tool call it makes

read_named(device: "dmg110-1", keys: ["voltage_l1_n", "voltage_l2_n", "voltage_l3_n"])

Have this device? Verify the map.

Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.

Collecting from many devices?

Proxus reads Modbus TCP and RTU devices next to the machines, keeps the history and delivers the values to dashboards, databases and AI.

Modbus in Proxus Industrial connectivity