Lovato Electric DMG210 Modbus register map
Also searched as: DMG 210
55 Modbus registers of the Lovato Electric DMG210, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from DMG series digital multimeters-analyzers: Modbus communication protocol (07/02/2022).
Lovato DMG210 multimeter with built-in RS485; scaled 32-bit integers.
- Device type
- Power analyser
- Registers
- 55
- Interfaces
- Modbus RTU, ASCII
- Default unit ID
- 1
- Byte order (multi-register values)
- ABCD
- Serial settings
- 9600 baud, 8 data bits, no parity, 1 stop bit
- Registers per read
- 64
Hardware verification
Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.
Connection notes
- Addresses here are the table addresses minus one, as the protocol document requires (its example reads L2 active power, table address 0016H, with start address 0015H).
- Function 03 or 04 reads the measurements; 32-bit values are sent high word first, as the document's example response shows (00 01 FB 00 = 129792).
- Energy counters at 1A20H-1A32H are 2-word counters that roll over to 0 after 19,999,999.99 kWh; 4-word versions exist at 1B20H and up from software revision 07.
- Frequency is in Hz/100 on the DMG210.
Registers
Grouped as in the vendor document.
Voltage 8 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
L1 Phase Voltagevoltage_l1_n | 30002 | 0x0001 | uint32 | ABCD | V | × 0.01 |
L2 Phase Voltagevoltage_l2_n | 30004 | 0x0003 | uint32 | ABCD | V | × 0.01 |
L3 Phase Voltagevoltage_l3_n | 30006 | 0x0005 | uint32 | ABCD | V | × 0.01 |
L1-L2 Voltagevoltage_l1_l2 | 30014 | 0x000D | uint32 | ABCD | V | × 0.01 |
L2-L3 Voltagevoltage_l2_l3 | 30016 | 0x000F | uint32 | ABCD | V | × 0.01 |
L3-L1 Voltagevoltage_l3_l1 | 30018 | 0x0011 | uint32 | ABCD | V | × 0.01 |
Eqv. Phase Voltagevoltage_phase_equivalent | 30052 | 0x0033 | uint32 | ABCD | V | × 0.01 |
Eqv. Phase-To-Phase Voltagevoltage_phase_to_phase_equivalent | 30054 | 0x0035 | uint32 | ABCD | V | × 0.01 |
Current 5 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
L1 Currentcurrent_l1 | 30008 | 0x0007 | uint32 | ABCD | A | × 0.0001 |
L2 Currentcurrent_l2 | 30010 | 0x0009 | uint32 | ABCD | A | × 0.0001 |
L3 Currentcurrent_l3 | 30012 | 0x000B | uint32 | ABCD | A | × 0.0001 |
Eqv. Currentcurrent_equivalent | 30056 | 0x0037 | uint32 | ABCD | A | × 0.0001 |
Neutral Currentcurrent_n | 30072 | 0x0047 | uint32 | ABCD | A | × 0.0001 |
Power 12 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
L1 Active Poweractive_power_l1 | 30020 | 0x0013 | int32 | ABCD | W | × 0.01 |
L2 Active Poweractive_power_l2 | 30022 | 0x0015 | int32 | ABCD | W | × 0.01 |
L3 Active Poweractive_power_l3 | 30024 | 0x0017 | int32 | ABCD | W | × 0.01 |
L1 Reactive Powerreactive_power_l1 | 30026 | 0x0019 | int32 | ABCD | var | × 0.01 |
L2 Reactive Powerreactive_power_l2 | 30028 | 0x001B | int32 | ABCD | var | × 0.01 |
L3 Reactive Powerreactive_power_l3 | 30030 | 0x001D | int32 | ABCD | var | × 0.01 |
L1 Apparent Powerapparent_power_l1 | 30032 | 0x001F | uint32 | ABCD | VA | × 0.01 |
L2 Apparent Powerapparent_power_l2 | 30034 | 0x0021 | uint32 | ABCD | VA | × 0.01 |
L3 Apparent Powerapparent_power_l3 | 30036 | 0x0023 | uint32 | ABCD | VA | × 0.01 |
Eqv. Active Poweractive_power_equivalent | 30058 | 0x0039 | int32 | ABCD | W | × 0.01 |
Eqv. Reactive Powerreactive_power_equivalent | 30060 | 0x003B | int32 | ABCD | var | × 0.01 |
Eqv. Apparent Powerapparent_power_equivalent | 30062 | 0x003D | uint32 | ABCD | VA | × 0.01 |
Frequency 1 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Frequencyfrequency | 30050 | 0x0031 | uint32 | ABCD | Hz | × 0.01 |
Energy 10 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Total imp. Active Energyactive_energy_imported_total | 36688 | 0x1A1F | uint32 | ABCD | kWh | × 0.01 |
Total exported Active Energyactive_energy_exported_total | 36690 | 0x1A21 | uint32 | ABCD | kWh | × 0.01 |
Total imp. Reactive Energyreactive_energy_imported_total | 36692 | 0x1A23 | uint32 | ABCD | kvarh | × 0.01 |
Total exp. Reactive Energyreactive_energy_exported_total | 36694 | 0x1A25 | uint32 | ABCD | kvarh | × 0.01 |
Total Apparent Energyapparent_energy_total | 36696 | 0x1A27 | uint32 | ABCD | kVAh | × 0.01 |
Partial imp. Active Energyactive_energy_imported_partial | 36698 | 0x1A29 | uint32 | ABCD | kWh | × 0.01 |
Partial exp. Active Energyactive_energy_exported_partial | 36700 | 0x1A2B | uint32 | ABCD | kWh | × 0.01 |
Partial imp. Reactive Energyreactive_energy_imported_partial | 36702 | 0x1A2D | uint32 | ABCD | kvarh | × 0.01 |
Partial exp Reactive Energyreactive_energy_exported_partial | 36704 | 0x1A2F | uint32 | ABCD | kvarh | × 0.01 |
Partial Apparent Energyapparent_energy_partial | 36706 | 0x1A31 | uint32 | ABCD | kVAh | × 0.01 |
Status 1 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Phase sequencephase_sequence | 38308 | 0x2073 | uint16 |
Power factor 4 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
L1 Power Factorpower_factor_l1 | 30038 | 0x0025 | int32 | ABCD | × 0.0001 | |
L2 Power Factorpower_factor_l2 | 30040 | 0x0027 | int32 | ABCD | × 0.0001 | |
L3 Power Factorpower_factor_l3 | 30042 | 0x0029 | int32 | ABCD | × 0.0001 | |
Eqv Power Factorpower_factor_equivalent | 30064 | 0x003F | int32 | ABCD | × 0.0001 |
Quality 3 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Phase-Phase Voltage Asymmetryvoltage_asymmetry_phase_phase | 30066 | 0x0041 | uint32 | ABCD | % | × 0.01 |
Phase-Neutral Voltage Asymmetryvoltage_asymmetry_phase_neutral | 30068 | 0x0043 | uint32 | ABCD | % | × 0.01 |
Current Asymmetrycurrent_asymmetry | 30070 | 0x0045 | uint32 | ABCD | % | × 0.01 |
Harmonics 9 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
L1 Voltage Thdthd_voltage_l1 | 30084 | 0x0053 | uint32 | ABCD | % | × 0.01 |
L2 Voltage Thdthd_voltage_l2 | 30086 | 0x0055 | uint32 | ABCD | % | × 0.01 |
L3 Voltage Thdthd_voltage_l3 | 30088 | 0x0057 | uint32 | ABCD | % | × 0.01 |
L1 Current Thdthd_current_l1 | 30090 | 0x0059 | uint32 | ABCD | % | × 0.01 |
L2 Current Thdthd_current_l2 | 30092 | 0x005B | uint32 | ABCD | % | × 0.01 |
L3 Current Thdthd_current_l3 | 30094 | 0x005D | uint32 | ABCD | % | × 0.01 |
L1-2 Voltage Thdthd_voltage_l1_l2 | 30096 | 0x005F | uint32 | ABCD | % | × 0.01 |
L2-3 Voltage Thdthd_voltage_l2_l3 | 30098 | 0x0061 | uint32 | ABCD | % | × 0.01 |
L3-1 Voltage Thdthd_voltage_l3_l1 | 30100 | 0x0063 | uint32 | ABCD | % | × 0.01 |
Counters 2 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Total Hour meterhour_meter_total | 37680 | 0x1DFF | uint32 | ABCD | s | |
Partial Hour meterhour_meter_partial | 37682 | 0x1E01 | uint32 | ABCD | s |
Source documents
- DMG series digital multimeters-analyzers: Modbus communication protocol , Lovato Electric, I317IGB02_22, 07/02/2022 (accessed 2026-11-09) Table 2 (pages 9-14): instantaneous measures, THD, energy counters, hour meters, phase sequence.
Read it by name
Read the DMG210 with an AI assistant
The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.
This device speaks Modbus RTU: reach it through a Modbus TCP gateway and use the gateway’s address with the device’s unit ID.
proxus-mcp.json
{
"devices": {
"dmg210-1": {
"protocol": "modbus-tcp",
"host": "192.168.10.40",
"unit_id": 1,
"map": "lovato-electric/dmg210"
}
}
} Ask your assistant
Read voltage_l1_n, voltage_l2_n, voltage_l3_n from dmg210-1.
The tool call it makes
read_named(device: "dmg210-1", keys: ["voltage_l1_n", "voltage_l2_n", "voltage_l3_n"]) Have this device? Verify the map.
Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.
Collecting from many devices?
Proxus reads Modbus TCP and RTU devices next to the machines, keeps the history and delivers the values to dashboards, databases and AI.