Schneider Electric ATV320 Modbus register map
Also searched as: Altivar Machine ATV320 · ATV320U · ATV320D
1,071 Modbus registers of the Schneider Electric ATV320, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from ATV320 - communication parameters addresses (V3.5).
Altivar Machine ATV320 variable speed drive; every parameter is a 16-bit holding register at its logic address.
- Device type
- Variable speed drive
- Registers
- 1,071
- Interfaces
- Modbus RTU, Modbus TCP
- Byte order (multi-register values)
- ABCD
- Serial settings
- 19200 baud, 8 data bits, even parity, 1 stop bit
Hardware verification
Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.
Connection notes
- The Modbus address of the drive is OFF from the factory; set [Modbus Address] (Add) before connecting.
- Modbus TCP needs an Ethernet communication module.
- Parameter codes (ETA, CMD, LFR...) are in each register's notes; the drive's display uses the same codes.
- Writing CMD or setpoints moves the motor. Read-only access is the safe default.
Registers
Grouped as in the vendor document. Measurement, energy and identity groups are shown (57 registers); open any other group to load it.
Actual values parameters 11 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Output velocityrfrd | 48605 | 0x219C | int16 | rpm | ||
Output frequencyrfr | 43203 | 0x0C82 | int16 | Hz | × 0.1 | |
Motor torqueotr | 43206 | 0x0C85 | int16 | % | × 0.1 | |
Motor currentlcr | 43205 | 0x0C84 | uint16 | A | × 0.1 | |
Motor voltageuop | 43209 | 0x0C88 | uint16 | V | ||
Motor poweropr | 43212 | 0x0C8B | int16 | % | ||
AO1 physical value without filtersao1 | 45296 | 0x14AF | int16 | |||
Motor speedspd | 412005 | 0x2EE4 | uint16 | |||
PLC encoder pulsepuc | 45612 | 0x15EB | uint16 | |||
Output value Customerspd1 | 412009 | 0x2EE8 | uint16 | × 0.01 | ||
Ratio D-Axis Current Errorrdae | 49677 | 0x25CC | int16 | % | × 0.1 |
Measurement parameters 14 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Line mains voltageuln | 43208 | 0x0C87 | uint16 | V | × 0.1 | |
Drive thermal statethd | 43210 | 0x0C89 | uint16 | % | ||
Motor thermal statethr | 49631 | 0x259E | uint16 | % | ||
Motor run timerth | 43232 | 0x0C9F | uint16 | |||
Power on timepth | 43234 | 0x0CA1 | uint16 | |||
AI1 physical value without filtersai1 | 45292 | 0x14AB | int16 | V | × 0.001 | |
AI2 physical value without filtersai2 | 45293 | 0x14AC | int16 | V | × 0.001 | |
AI3 physical value without filtersai3 | 45294 | 0x14AD | int16 | mA | × 0.001 | |
AI1 input physical image (MAX = 8192)ai1i | 45223 | 0x1466 | int16 | |||
AI2 input physical image (MAX = 8192)ai2i | 45224 | 0x1467 | int16 | |||
AI3 input physical image (MAX = 8192)ai3i | 45225 | 0x1468 | int16 | |||
Power consumptionaph | 43231 | 0x0C9E | uint16 | |||
IGBT alarm countertac | 43236 | 0x0CA3 | uint16 | s | ||
Min IGBT frequency timetac2 | 43243 | 0x0CAA | uint16 | s |
Status parameters 20 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Drivecom state registereta | 43202 | 0x0C81 | bitfield16 | |||
Drive statehmis | 43241 | 0x0CA8 | uint16 | |||
Extended state registereti | 43207 | 0x0C86 | bitfield16 | |||
Reference channelcrc | 48442 | 0x20F9 | bitfield16 | |||
Active command channelccc | 48443 | 0x20FA | bitfield16 | |||
Active configurationcnfs | 48021 | 0x1F54 | uint16 | |||
Tune selectionstun | 49618 | 0x2591 | uint16 | |||
Status of motor tune in term of saliencysmot | 49646 | 0x25AD | uint16 | |||
EtherCAT slave statusecss | 46691 | 0x1A22 | uint16 | |||
EtherCAT addressecaa | 46693 | 0x1A24 | uint16 | |||
DRIVECOM : Status wordetad | 48604 | 0x219B | bitfield16 | |||
Logic result status 1 (PSL 000-015)lrs1 | 43251 | 0x0CB2 | bitfield16 | |||
Logic result status 2 (PSL 016-031)lrs2 | 43252 | 0x0CB3 | bitfield16 | |||
Logic result status 3 (PSL 032-047)lrs3 | 43253 | 0x0CB4 | bitfield16 | |||
Logic result status 4 (PSL 048-063)lrs4 | 43254 | 0x0CB5 | bitfield16 | |||
Logic result status 5 (PSL 064-079)lrs5 | 43255 | 0x0CB6 | bitfield16 | |||
Logic result status 6 (PSL 080-095)lrs6 | 43256 | 0x0CB7 | bitfield16 | |||
Logic result status 7 (PSL 096-111)lrs7 | 43257 | 0x0CB8 | bitfield16 | |||
Logic result status 8 (PSL 112-127)lrs8 | 43258 | 0x0CB9 | bitfield16 | |||
IGBT alarm Nbntj | 43242 | 0x0CA9 | uint16 |
Identification parameters 12 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Drive nominal ratingncv | 43012 | 0x0BC3 | uint16 | |||
Drive mains voltagevcal | 43013 | 0x0BC4 | uint16 | |||
Drive nominal currentinv | 43018 | 0x0BC9 | uint16 | A | × 0.1 | |
Drive software versionvdp | 43303 | 0x0CE6 | uint16 | |||
Device name (char 1 and 2)pan0 | 43341 | 0x0D0C | uint16 | |||
Device name (char 3 and 4)pan1 | 43342 | 0x0D0D | uint16 | |||
Device name (char 5 and 6)pan2 | 43343 | 0x0D0E | uint16 | |||
Device name (char 7 and 8)pan3 | 43344 | 0x0D0F | uint16 | |||
Device name (char 9 and 10)pan4 | 43345 | 0x0D10 | uint16 | |||
Device name (char 11 and 12)pan5 | 43346 | 0x0D11 | uint16 | |||
Device name (char 13 and 14)pan6 | 43347 | 0x0D12 | uint16 | |||
Device name (char 15 and 16)pan7 | 43348 | 0x0D13 | uint16 |
Control parameters 3 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Setpoint parameters 6 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Reference parameters 8 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
I/O parameters 13 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Fault parameters 8 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
History parameters 154 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Communication parameters 19 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
CiA 402 settings 10 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Configuration management 3 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Parameter set switching 64 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Configuration and settings 524 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Safety function 153 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Function blocks 49 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|
Source documents
- ATV320 - communication parameters addresses , Schneider Electric, NVE41316, V3.5 (accessed 2026-10-31)
- Altivar Machine ATV320 Modbus Serial Link Manual , Schneider Electric, NVE41308, 01 (accessed 2026-10-31) Serial defaults, and the example frame showing that logic addresses are sent unchanged.
Read it by name
Read the ATV320 with an AI assistant
The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.
proxus-mcp.json
{
"devices": {
"atv320-1": {
"protocol": "modbus-tcp",
"host": "192.168.10.40",
"unit_id": 1,
"map": "schneider-electric/atv320"
}
}
} Ask your assistant
Read rfrd, rfr, otr from atv320-1.
The tool call it makes
read_named(device: "atv320-1", keys: ["rfrd", "rfr", "otr"]) Have this device? Verify the map.
Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.