Skip to content
Proxus 2.0.1 Licence and sign-in fixes after the 2.0 upgrade Release notes

Siemens PAC3220 Modbus register map

Also searched as: SENTRON PAC3220 · SENTRON PAC3120 · PAC3120 · 7KM3220-0BA01-1DA0 · 7KM3220-1BA01-1EA0

91 Modbus registers of the Siemens PAC3220, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from SENTRON 7KM PAC3120 and PAC3220 Power Monitoring Device Equipment Manual (10/2019).

SENTRON PAC3120/PAC3220 power monitoring devices; measurements are 32-bit floats, energy counters 64-bit floats.

Device type
Power analyser
Registers
91
Interfaces
Modbus TCP, Modbus RTU
Byte order (multi-register values)
ABCD
Serial settings
19200 baud, 8 data bits, no parity, 2 stop bits; address 126 (PAC3120)

Hardware verification

Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.

Verify it on your device What the levels mean

Connection notes

  • Addresses are the manual's offsets, sent unchanged, the convention of this repository's PAC3200 map; the manual has no example frame to settle it.
  • Function code 3 or 4 reads the same registers; reading from the middle of a multi-register value is refused.
  • The PAC3220 has Modbus TCP built in (RTU with the PAC RS485 expansion module); the PAC3120 has Modbus RTU built in.
  • The status registers at 233-239 for 4DI/2DO expansion modules exist on the PAC3220 only and are left out.

Registers

Grouped as in the vendor document.

Instantaneous 36 registers
Name and key Reference Address Type Byte order Unit Scale
Voltage L1-Nvoltage_l1_n 40002 0x0001 float32 ABCD V
Voltage L2-Nvoltage_l2_n 40004 0x0003 float32 ABCD V
Voltage L3-Nvoltage_l3_n 40006 0x0005 float32 ABCD V
Voltage L1-L2voltage_l1_l2 40008 0x0007 float32 ABCD V
Voltage L2-L3voltage_l2_l3 40010 0x0009 float32 ABCD V
Voltage L3-L1voltage_l3_l1 40012 0x000B float32 ABCD V
Current L1current_l1 40014 0x000D float32 ABCD A
Current L2current_l2 40016 0x000F float32 ABCD A
Current L3current_l3 40018 0x0011 float32 ABCD A
Apparent power L1apparent_power_l1 40020 0x0013 float32 ABCD VA
Apparent power L2apparent_power_l2 40022 0x0015 float32 ABCD VA
Apparent power L3apparent_power_l3 40024 0x0017 float32 ABCD VA
Active power L1active_power_l1 40026 0x0019 float32 ABCD W
Active power L2active_power_l2 40028 0x001B float32 ABCD W
Active power L3active_power_l3 40030 0x001D float32 ABCD W
Reactive power L1 (VAR1)reactive_power_l1 40032 0x001F float32 ABCD var
Power factor L1power_factor_l1 40038 0x0025 float32 ABCD
Power factor L2power_factor_l2 40040 0x0027 float32 ABCD
Power factor L3power_factor_l3 40042 0x0029 float32 ABCD
THD-R voltage L1thd_r_voltage_l1 40044 0x002B float32 ABCD %
THD-R voltage L2thd_r_voltage_l2 40046 0x002D float32 ABCD %
THD-R voltage L3thd_r_voltage_l3 40048 0x002F float32 ABCD %
THD-R current L1thd_r_current_l1 40050 0x0031 float32 ABCD %
THD-R current L2thd_r_current_l2 40052 0x0033 float32 ABCD %
THD-R current L3thd_r_current_l3 40054 0x0035 float32 ABCD %
Frequencyfrequency 40056 0x0037 float32 ABCD Hz
Average voltage L-Naverage_voltage_l_n 40058 0x0039 float32 ABCD V
Average voltage L-Laverage_voltage_l_l 40060 0x003B float32 ABCD V
Average currentaverage_current 40062 0x003D float32 ABCD A
Total apparent powertotal_apparent_power 40064 0x003F float32 ABCD VA
Total active powertotal_active_power 40066 0x0041 float32 ABCD W
Total reactive powertotal_reactive_power 40068 0x0043 float32 ABCD var
Total power factortotal_power_factor 40070 0x0045 float32 ABCD
Amplitude unbalance voltageamplitude_unbalance_voltage 40072 0x0047 float32 ABCD %
Amplitude unbalance currentamplitude_unbalance_current 40074 0x0049 float32 ABCD %
Current Ncurrent_n 40224 0x00DF float32 ABCD A
Energy 10 registers
Name and key Reference Address Type Byte order Unit Scale
Total active energy import, tariff 1active_import_energy_t1 40802 0x0321 float64 ABCD Wh
Total active energy import, tariff 2active_import_energy_t2 40806 0x0325 float64 ABCD Wh
Total active energy export, tariff 1active_export_energy_t1 40810 0x0329 float64 ABCD Wh
Total active energy export, tariff 2active_export_energy_t2 40814 0x032D float64 ABCD Wh
Total reactive energy import, tariff 1reactive_import_energy_t1 40818 0x0331 float64 ABCD varh
Total reactive energy import, tariff 2reactive_import_energy_t2 40822 0x0335 float64 ABCD varh
Total reactive energy export, tariff 1reactive_export_energy_t1 40826 0x0339 float64 ABCD varh
Total reactive energy export, tariff 2reactive_export_energy_t2 40830 0x033D float64 ABCD varh
Total apparent energy, tariff 1apparent_energy_t1 40834 0x0341 float64 ABCD VAh
Total apparent energy, tariff 2apparent_energy_t2 40838 0x0345 float64 ABCD VAh
Phase energy 30 registers
Name and key Reference Address Type Byte order Unit Scale
L1 active energy import, tariff 1l1_active_import_energy_t1 40842 0x0349 float64 ABCD Wh
L1 active energy import, tariff 2l1_active_import_energy_t2 40846 0x034D float64 ABCD Wh
L1 active energy export, tariff 1l1_active_export_energy_t1 40850 0x0351 float64 ABCD Wh
L1 active energy export, tariff 2l1_active_export_energy_t2 40854 0x0355 float64 ABCD Wh
L1 reactive energy import, tariff 1l1_reactive_import_energy_t1 40858 0x0359 float64 ABCD varh
L1 reactive energy import, tariff 2l1_reactive_import_energy_t2 40862 0x035D float64 ABCD varh
L1 reactive energy export, tariff 1l1_reactive_export_energy_t1 40866 0x0361 float64 ABCD varh
L1 reactive energy export, tariff 2l1_reactive_export_energy_t2 40870 0x0365 float64 ABCD varh
L1 apparent energy, tariff 1l1_apparent_energy_t1 40874 0x0369 float64 ABCD VAh
L1 apparent energy, tariff 2l1_apparent_energy_t2 40878 0x036D float64 ABCD VAh
L2 active energy import, tariff 1l2_active_import_energy_t1 40882 0x0371 float64 ABCD Wh
L2 active energy import, tariff 2l2_active_import_energy_t2 40886 0x0375 float64 ABCD Wh
L2 active energy export, tariff 1l2_active_export_energy_t1 40890 0x0379 float64 ABCD Wh
L2 active energy export, tariff 2l2_active_export_energy_t2 40894 0x037D float64 ABCD Wh
L2 reactive energy import, tariff 1l2_reactive_import_energy_t1 40898 0x0381 float64 ABCD varh
L2 reactive energy import, tariff 2l2_reactive_import_energy_t2 40902 0x0385 float64 ABCD varh
L2 reactive energy export, tariff 1l2_reactive_export_energy_t1 40906 0x0389 float64 ABCD varh
L2 reactive energy export, tariff 2l2_reactive_export_energy_t2 40910 0x038D float64 ABCD varh
L2 apparent energy, tariff 1l2_apparent_energy_t1 40914 0x0391 float64 ABCD VAh
L2 apparent energy, tariff 2l2_apparent_energy_t2 40918 0x0395 float64 ABCD VAh
L3 active energy import, tariff 1l3_active_import_energy_t1 40922 0x0399 float64 ABCD Wh
L3 active energy import, tariff 2l3_active_import_energy_t2 40926 0x039D float64 ABCD Wh
L3 active energy export, tariff 1l3_active_export_energy_t1 40930 0x03A1 float64 ABCD Wh
L3 active energy export, tariff 2l3_active_export_energy_t2 40934 0x03A5 float64 ABCD Wh
L3 reactive energy import, tariff 1l3_reactive_import_energy_t1 40938 0x03A9 float64 ABCD varh
L3 reactive energy import, tariff 2l3_reactive_import_energy_t2 40942 0x03AD float64 ABCD varh
L3 reactive energy export, tariff 1l3_reactive_export_energy_t1 40946 0x03B1 float64 ABCD varh
L3 reactive energy export, tariff 2l3_reactive_export_energy_t2 40950 0x03B5 float64 ABCD varh
L3 apparent energy, tariff 1l3_apparent_energy_t1 40954 0x03B9 float64 ABCD VAh
L3 apparent energy, tariff 2l3_apparent_energy_t2 40958 0x03BD float64 ABCD VAh
Status 5 registers
Name and key Reference Address Type Byte order Unit Scale
Limit violationslimit_violations 40204 0x00CB bitfield
Device diagnostics and device statusdevice_status 40206 0x00CD bitfield
Digital outputs statusdigital_outputs_status 40208 0x00CF bitfield
Digital inputs statusdigital_inputs_status 40210 0x00D1 bitfield
Active tariffactive_tariff 40212 0x00D3 uint32 ABCD
Counters 4 registers
Name and key Reference Address Type Byte order Unit Scale
Operating hours counteroperating_hours_counter 40214 0x00D5 uint32 ABCD s
Counter (configurable)universal_counter 40216 0x00D7 uint32 ABCD
Counter basic parameter changesparameter_changes_basic 40218 0x00D9 uint32 ABCD
Counter all parameter changesparameter_changes_all 40220 0x00DB uint32 ABCD
Settings 6 registers
Name and key Reference Address Type Byte order Unit Scale
Connection typeconnection_type 450002 0xC351 uint32 ABCD
Voltage measurement using voltage transformervoltage_transformer_used 450004 0xC353 uint32 ABCD
Primary voltagevt_primary_voltage 450006 0xC355 uint32 ABCD V
Secondary voltagevt_secondary_voltage 450008 0xC357 uint32 ABCD V
Primary currentct_primary_current 450012 0xC35B uint32 ABCD A
Secondary currentct_secondary_current 450014 0xC35D uint32 ABCD A

Source documents

View this map on GitHub (YAML)

Read it by name

Read the PAC3220 with an AI assistant

The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.

proxus-mcp.json

{
  "devices": {
    "pac3220-1": {
      "protocol": "modbus-tcp",
      "host": "192.168.10.40",
      "unit_id": 1,
      "map": "siemens/pac3220"
    }
  }
}

Ask your assistant

Read voltage_l1_n, voltage_l2_n, voltage_l3_n from pac3220-1.

The tool call it makes

read_named(device: "pac3220-1", keys: ["voltage_l1_n", "voltage_l2_n", "voltage_l3_n"])

Have this device? Verify the map.

Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.

Collecting from many devices?

Proxus reads Modbus TCP and RTU devices next to the machines, keeps the history and delivers the values to dashboards, databases and AI.

Modbus in Proxus Industrial connectivity