Siemens SINAMICS V20 Modbus register map

Also searched as: V20 · SINAMICS V20 inverter · 6SL3210-5BB · 6SL3210-5BE

77 Modbus registers of the Siemens SINAMICS V20, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from SINAMICS V20 Inverter Operating Instructions (01/2018).

SINAMICS V20 inverter over Modbus RTU on its RS485 port; 16-bit holding registers with fixed scaling factors.

Device type
Variable speed drive
Registers
77
Interfaces
Modbus RTU
Default unit ID
1
Byte order (multi-register values)
ABCD
Serial settings
9600 baud, 8 data bits, even parity, 1 stop bit

Hardware verification

Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.

Verify it on your device What the levels mean

Connection notes

  • The manual lists each register twice, as the inverter register number and as the 40001-based Modbus number; the address here is the inverter number, which is the Modbus number minus 40001.
  • Set P2023 = 2 (Modbus) and power-cycle; P0700 = 5 makes RS485 the command source. Address P2021 (default 1), baud rate P2010, parity P2034, stop bits P2035.
  • Scaled registers hold value x scaling factor (factor 100 is scale 0.01 here).
  • On/off registers list the source's on text as 1 and its off text as 0.
  • Most values also appear in a second register set from 40200 on; only registers that the first set lacks are listed from it.
  • Writing control registers or setpoints moves the motor. Read-only access is the safe default.

Registers

Grouped as in the vendor document.

Status 11 registers
Name and key Reference Address Type Byte order Unit Scale
Forward/reversestatus_forward_reverse 40034 0x0021 uint16
Stop/runstatus_stop_run 40035 0x0022 uint16
Run at maximum frequencystatus_at_max_frequency 40036 0x0023 uint16
Control modestatus_control_mode 40037 0x0024 uint16
Enabledstatus_enabled 40038 0x0025 uint16
Ready to runstatus_ready_to_run 40039 0x0026 uint16
Faultstatus_fault 40054 0x0035 uint16
Warningstatus_warning 40059 0x003A uint16
Status word (ZSW)zsw 40110 0x006D bitfield16
Actual speed (HIW)hiw 40111 0x006E int16
Hand/autohand_auto 40349 0x015C uint16
Identification 3 registers
Name and key Reference Address Type Byte order Unit Scale
Rated powerrated_power 40032 0x001F uint16 kW × 0.01
Inverter versioninverter_version 40061 0x003C uint16 × 0.01
Inverter modelinverter_model 40062 0x003D uint16
Settings 10 registers
Name and key Reference Address Type Byte order Unit Scale
Watchdog timewatchdog_time 40001 0x0000 uint16 ms
Watchdog actionwatchdog_action 40002 0x0001 uint16
Current limitcurrent_limit 40010 0x0009 uint16 % × 0.1
Acceleration timeacceleration_time 40011 0x000A uint16 s × 0.01
Deceleration timedeceleration_time 40012 0x000B uint16 s × 0.01
Reference frequencyreference_frequency 40016 0x000F uint16 Hz × 0.01
Fixed frequency 1fixed_frequency_1 40325 0x0144 int16 Hz × 0.01
Fixed frequency 2fixed_frequency_2 40326 0x0145 int16 Hz × 0.01
Fixed frequency 3fixed_frequency_3 40327 0x0146 int16 Hz × 0.01
Fixed frequency 4fixed_frequency_4 40328 0x0147 int16 Hz × 0.01
Control 7 registers
Name and key Reference Address Type Byte order Unit Scale
Frequency setpointfrequency_setpoint 40003 0x0002 uint16 % × 0.01
Run enablerun_enable 40004 0x0003 uint16
Forward/reverse commandforward_reverse_command 40005 0x0004 uint16
Start commandstart_command 40006 0x0005 uint16
Fault acknowledgementfault_acknowledge 40007 0x0006 uint16
Control word (STW)stw 40100 0x0063 bitfield16
Speed setpoint (HSW)hsw 40101 0x0064 int16
Pid 12 registers
Name and key Reference Address Type Byte order Unit Scale
PID setpoint referencepid_setpoint_reference 40008 0x0007 int16 % × 0.01
PID enablepid_enable 40009 0x0008 uint16
PID upper limitpid_upper_limit 40017 0x0010 int16 % × 0.01
PID lower limitpid_lower_limit 40018 0x0011 int16 % × 0.01
PID proportional gainpid_proportional_gain 40019 0x0012 uint16 × 0.001
PID integral gainpid_integral_gain 40020 0x0013 uint16 s
PID differential gainpid_differential_gain 40021 0x0014 uint16
PID feedback gainpid_feedback_gain 40022 0x0015 uint16 % × 0.01
PID low passpid_low_pass 40023 0x0016 uint16 × 0.01
PID setpoint outputpid_setpoint_output 40045 0x002C int16 % × 0.01
PID outputpid_output 40046 0x002D int16 % × 0.01
PID feedbackpid_feedback 40047 0x002E int16 % × 0.01
I/O 13 registers
Name and key Reference Address Type Byte order Unit Scale
Digital output 1digital_output_1 40014 0x000D uint16
Digital output 2digital_output_2 40015 0x000E uint16
Analog input 1analog_input_1 40040 0x0027 int16 % × 0.01
Analog input 2analog_input_2 40041 0x0028 int16 % × 0.01
Analog output 1analog_output_1 40042 0x0029 int16 % × 0.01
Digital input 1digital_input_1 40048 0x002F uint16
Digital input 2digital_input_2 40049 0x0030 uint16
Digital input 3digital_input_3 40050 0x0031 uint16
Digital input 4digital_input_4 40051 0x0032 uint16
Digital output 3digital_output_3 40202 0x00C9 uint16
Digital output 4digital_output_4 40203 0x00CA uint16
Digital input 5digital_input_5 40244 0x00F3 uint16
Digital input 6digital_input_6 40245 0x00F4 uint16
Actual values 11 registers
Name and key Reference Address Type Byte order Unit Scale
Frequency outputoutput_frequency 40024 0x0017 int16 Hz × 0.01
Speedspeed 40025 0x0018 int16 rpm
Current filteredcurrent_filtered 40026 0x0019 uint16 A × 0.01
Torquetorque 40027 0x001A int16 Nm × 0.01
Actual poweractual_power 40028 0x001B uint16 kW × 0.01
Total kWhtotal_kwh 40029 0x001C uint16 kWh
DC bus voltagedc_bus_voltage 40030 0x001D uint16 V
Referencefrequency_reference 40031 0x001E int16 Hz × 0.01
Voltage outputoutput_voltage 40033 0x0020 uint16 V
Actual frequencyactual_frequency_percent 40044 0x002B int16 % × 0.01
Current unfilteredcurrent_unfiltered 40350 0x015D uint16 A × 0.01
Faults 9 registers
Name and key Reference Address Type Byte order Unit Scale
Last faultlast_fault 40055 0x0036 uint16
Fault number, index 1fault_index_1 40056 0x0037 uint16
Fault number, index 2fault_index_2 40057 0x0038 uint16
Fault number, index 3fault_index_3 40058 0x0039 uint16
Last warninglast_warning 40060 0x003B uint16
Fault number, index 4fault_index_4 40404 0x0193 uint16
Fault number, index 5fault_index_5 40405 0x0194 uint16
Fault number, index 6fault_index_6 40406 0x0195 uint16
Fault number, index 7fault_index_7 40407 0x0196 uint16
Diagnostics 1 registers
Name and key Reference Address Type Byte order Unit Scale
Parameter error codeparameter_error_code 40499 0x01F2 uint16

Source documents

View this map on GitHub (YAML)

Read it by name

Read the SINAMICS V20 with an AI assistant

The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.

This device speaks Modbus RTU: reach it through a Modbus TCP gateway and use the gateway’s address with the device’s unit ID.

proxus-mcp.json

{
  "devices": {
    "sinamics-1": {
      "protocol": "modbus-tcp",
      "host": "192.168.10.40",
      "unit_id": 1,
      "map": "siemens/sinamics-v20"
    }
  }
}

Ask your assistant

Read rated_power from sinamics-1.

The tool call it makes

read_named(device: "sinamics-1", keys: ["rated_power"])

Have this device? Verify the map.

Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.

Collecting from many devices?

Proxus reads Modbus TCP and RTU devices next to the machines, keeps the history and delivers the values to dashboards, databases and AI.

Modbus in Proxus Industrial connectivity