Siemens SINAMICS G120C Modbus register map
Also searched as: G120C · G120C USS/MB · SINAMICS G120C USS/MB
63 Modbus registers of the Siemens SINAMICS G120C, with the address on the wire, the 30001-style reference, data type, byte order, unit and scale. Transcribed from SINAMICS G120 Fieldbuses Function Manual (11/2020, FW V4.7 SP13).
SINAMICS G120C converter (USS/MB version) over Modbus RTU on RS485; 16-bit holding registers with fixed scaling factors.
- Device type
- Variable speed drive
- Registers
- 63
- Interfaces
- Modbus RTU
- Default unit ID
- 1
- Byte order (multi-register values)
- ABCD
- Serial settings
- 19200 baud, 8 data bits, even parity, 1 stop bit
Hardware verification
Not yet verified on hardware. The map is transcribed from the vendor document and checked against it by script; check the first readings against the device display.
Connection notes
- The manual numbers holding registers from 40001; the address here is the register minus 40001 (its example frames read 40110 at 0x006D and write 40100 at 0x0063).
- Select Modbus with p2030 = 2; address p2021 (or the address switch), baud rate p2020, parity p2031.
- Scaled registers hold value x scaling factor (factor 100 is scale 0.01 here). The main setpoint and actual value are unscaled process data.
- On/off registers list the source's on text as 1 and its off text as 0.
- The same function manual lists this register table for G120 Control Units CU230P-2, CU240B-2, CU240E-2 and CU250S-2; check their own manuals before reusing this map.
- Registers 40601-40722 (acyclic DS47 access) and 40800-40811 (multi-pump control) are left out.
- Writing the control word or setpoint moves the motor. Read-only access is the safe default.
Registers
Grouped as in the vendor document.
Status 3 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Status word (ZSW1)zsw1 | 40110 | 0x006D | bitfield16 | |||
Main actual valuemain_actual_value | 40111 | 0x006E | int16 | |||
Control prioritycontrol_priority | 40349 | 0x015C | uint16 |
Identification 3 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Powerstack numberpowerstack_number | 40300 | 0x012B | uint16 | |||
Converter firmwareconverter_firmware | 40301 | 0x012C | uint16 | |||
Rated powerrated_power | 40320 | 0x013F | uint16 | kW | × 0.01 |
Control 2 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Control word (STW1)stw1 | 40100 | 0x0063 | bitfield16 | |||
Main setpointmain_setpoint | 40101 | 0x0064 | int16 |
I/O 19 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
DO 0digital_output_0 | 40200 | 0x00C7 | uint16 | |||
DO 1digital_output_1 | 40201 | 0x00C8 | uint16 | |||
DO 2digital_output_2 | 40202 | 0x00C9 | uint16 | |||
AO 0analog_output_0 | 40220 | 0x00DB | int16 | % | × 0.01 | |
AO 1analog_output_1 | 40221 | 0x00DC | int16 | % | × 0.01 | |
AO 2analog_output_2 | 40222 | 0x00DD | int16 | % | × 0.01 | |
DI 0digital_input_0 | 40240 | 0x00EF | uint16 | |||
DI 1digital_input_1 | 40241 | 0x00F0 | uint16 | |||
DI 2digital_input_2 | 40242 | 0x00F1 | uint16 | |||
DI 3digital_input_3 | 40243 | 0x00F2 | uint16 | |||
DI 4digital_input_4 | 40244 | 0x00F3 | uint16 | |||
DI 5digital_input_5 | 40245 | 0x00F4 | uint16 | |||
AI 0analog_input_0 | 40260 | 0x0103 | int16 | % | × 0.01 | |
AI 1analog_input_1 | 40261 | 0x0104 | int16 | % | × 0.01 | |
AI 2analog_input_2 | 40262 | 0x0105 | int16 | % | × 0.01 | |
AI 3analog_input_3 | 40263 | 0x0106 | int16 | % | × 0.01 | |
AO 0 (write)analog_output_0_setting | 40523 | 0x020A | int16 | % | × 0.01 | |
AO 1 (write)analog_output_1_setting | 40524 | 0x020B | int16 | % | × 0.01 | |
AO 2 (write)analog_output_2_setting | 40525 | 0x020C | int16 | % | × 0.01 |
Settings 4 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Current limitcurrent_limit | 40321 | 0x0140 | uint16 | A | × 0.1 | |
Ramp-up timeramp_up_time | 40322 | 0x0141 | uint16 | s | × 0.01 | |
Ramp-down timeramp_down_time | 40323 | 0x0142 | uint16 | s | × 0.01 | |
Reference speedreference_speed | 40324 | 0x0143 | uint16 | rpm |
Actual values 9 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Speed setpointspeed_setpoint | 40340 | 0x0153 | int16 | rpm | ||
Actual speed valueactual_speed | 40341 | 0x0154 | int16 | rpm | ||
Output frequencyoutput_frequency | 40342 | 0x0155 | int16 | Hz | × 0.01 | |
Output voltageoutput_voltage | 40343 | 0x0156 | uint16 | V | ||
DC link voltagedc_link_voltage | 40344 | 0x0157 | uint16 | V | ||
Current actual valueactual_current | 40345 | 0x0158 | uint16 | A | × 0.01 | |
Actual torque valueactual_torque | 40346 | 0x0159 | int16 | Nm | × 0.01 | |
Actual active poweractual_active_power | 40347 | 0x015A | uint16 | kW | × 0.01 | |
Energy consumptionenergy_consumption | 40348 | 0x015B | uint16 | kWh |
Faults 10 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Fault number, index 0fault_number_0 | 40400 | 0x018F | uint16 | |||
Fault number, index 1fault_number_1 | 40401 | 0x0190 | uint16 | |||
Fault number, index 2fault_number_2 | 40402 | 0x0191 | uint16 | |||
Fault number, index 3fault_number_3 | 40403 | 0x0192 | uint16 | |||
Fault number, index 4fault_number_4 | 40404 | 0x0193 | uint16 | |||
Fault number, index 5fault_number_5 | 40405 | 0x0194 | uint16 | |||
Fault number, index 6fault_number_6 | 40406 | 0x0195 | uint16 | |||
Fault number, index 7fault_number_7 | 40407 | 0x0196 | uint16 | |||
Alarm numberalarm_number | 40408 | 0x0197 | uint16 | |||
Actual alarm codeactual_alarm_code | 40409 | 0x0198 | uint16 |
Diagnostics 1 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
PRM ERROR codeparameter_error_code | 40499 | 0x01F2 | uint16 |
Pid 12 registers
| Name and key | Reference | Address | Type | Byte order | Unit | Scale |
|---|---|---|---|---|---|---|
Technology controller enabletc_enable | 40500 | 0x01F3 | uint16 | |||
Technology controller MOPtc_mop | 40501 | 0x01F4 | int16 | % | × 0.01 | |
Technology controller actual value filter time constanttc_filter_time | 40510 | 0x01FD | uint16 | × 0.01 | ||
Technology controller actual value scalingtc_feedback_scaling | 40511 | 0x01FE | uint16 | % | × 0.01 | |
Technology controller proportional gaintc_proportional_gain | 40512 | 0x01FF | uint16 | × 0.001 | ||
Technology controller integral timetc_integral_time | 40513 | 0x0200 | uint16 | s | ||
Technology controller D-component time constanttc_derivative_time | 40514 | 0x0201 | uint16 | |||
Technology controller max. limittc_max_limit | 40515 | 0x0202 | int16 | % | × 0.01 | |
Technology controller min. limittc_min_limit | 40516 | 0x0203 | int16 | % | × 0.01 | |
Technology controller effective setpointtc_effective_setpoint | 40520 | 0x0207 | int16 | % | × 0.01 | |
Technology controller actual value after filtertc_actual_value | 40521 | 0x0208 | int16 | % | × 0.01 | |
Technology controller output signaltc_output | 40522 | 0x0209 | int16 | % | × 0.01 |
Source documents
- SINAMICS G120 Fieldbuses Function Manual , Siemens, A5E34229197B AG, 11/2020, FW V4.7 SP13 (accessed 2026-11-09) Section 5.4 Communication using Modbus RTU, tables 5-12 to 5-17 and the example frames in tables 5-20 and 5-23.
Read it by name
Read the SINAMICS G120C with an AI assistant
The Proxus Industrial MCP Server includes this map. Set it on the device, and Claude, Cursor or VS Code reads registers by key with the right type, byte order, scale and unit. It only reads.
This device speaks Modbus RTU: reach it through a Modbus TCP gateway and use the gateway’s address with the device’s unit ID.
proxus-mcp.json
{
"devices": {
"sinamics-1": {
"protocol": "modbus-tcp",
"host": "192.168.10.40",
"unit_id": 1,
"map": "siemens/sinamics-g120c"
}
}
} Ask your assistant
Read rated_power from sinamics-1.
The tool call it makes
read_named(device: "sinamics-1", keys: ["rated_power"]) Have this device? Verify the map.
Ask your assistant to run verify_device_map. It reads every register once, read-only, checks that the values are plausible and asks you to compare two values with the display. You get a report and a prefilled GitHub issue to submit; your name goes on this map’s verified list.
Collecting from many devices?
Proxus reads Modbus TCP and RTU devices next to the machines, keeps the history and delivers the values to dashboards, databases and AI.