Pipeline nodes
Every node of the pipeline editor with what it does, its settings, its outputs and the pipeline kinds it can be used in, plus the limits of a pipeline.
This page lists every node of the pipeline editor's Canvas tab. Each node has two names: the one in the palette (used as the heading here) and the one at the top of its settings panel (given after "Panel name"). The Build tab creates the same nodes from plain steps. How to build and publish a pipeline is in Pipelines.
Two kinds of pipeline
| Execution class | Runs | Starts from | Can use |
|---|---|---|---|
| Transport Pipeline | on each reading, before it is stored or sent anywhere. It can change, drop or set aside data. | exactly one Transport Input | the nodes marked T below |
| Automation | after the reading is stored. The stored data is not changed; the pipeline opens alarms, sends messages, writes to devices or calls APIs. | 1 to 8 source nodes | the nodes marked A below |
Outputs and errors
Most nodes have one output, out, and an error output. Routing nodes have their own outputs, listed with each node. When a node fails and nothing is connected to its error output:
- in an automation pipeline, processing of that event stops and the error is counted;
- in a transport pipeline, the pipeline's On error setting decides: Pass Original (default: the reading goes on unchanged), Drop or Quarantine.
Nodes without outputs (marked "ends the branch") are the last step of a branch.
Field names
Settings that name a field use a path: payload.<tag> for a tag value, metadata.<name>, attributes.<name>, topic, origin, device.*, gateway.* or hierarchy.*. A tag name starts with a letter or _ and has at most 80 characters. The device and gateway identity (device.id, gateway.id, metadata.DeviceId, metadata.GatewayId) cannot be changed or removed.
Under Which data (on sources) and Conditions (on Filter and Switch) you choose which readings a node handles: by device, gateway, device profile, protocol, place (enterprise, site, area, line or cell, equipment), tag, topic, a tag's value, type, unit or quality. Required tags (advanced) on a source limits the pipeline to devices that have those tags.
Sources
Transport Input
Panel name Incoming data. T. Starts the pipeline for each reading of a matching device, before it is stored or forwarded. Only one per pipeline.
| Setting | Values |
|---|---|
| Run on | Every value (default) or Only when the value changes. |
Telemetry Input
Panel name Device values. A. Starts the pipeline when devices send new tag values. Run on: Every value or Only when the value changes.
Device Status Input
Panel name Device status. A. Starts the pipeline when a device connects, disconnects or changes state. No settings besides Which data.
Gateway Status Input
Panel name Gateway status. A. Starts the pipeline when a gateway connects or disconnects.
Operational Log Input
Panel name System log. A. Starts the pipeline from platform log entries (warnings, errors).
Runtime Metrics Input
Panel name Runtime metrics. A. Starts the pipeline from the gateway's performance figures.
Schedule Input
Panel name Schedule. A. Starts the pipeline at fixed times.
| Setting | Values |
|---|---|
| Schedule | Five fields: minute, hour, day of month, month, day of week (0 to 7, both 0 and 7 are Sunday). *, lists (1,15), ranges (8-17) and steps (*/5) are allowed. Default */5 * * * *. |
| Time zone | Default UTC. |
The schedule is checked once a minute. Runs missed while the gateway was off are not made up.
No Data Input
Panel name No data. A. Notices when a device stops sending values, and when it starts again.
| Setting | Values |
|---|---|
| Silence threshold (minutes) | 1 to 10080. Default 5. |
Outputs missing and restored, each sent once per change. It is checked once a minute, so it can fire up to a minute after the threshold.
Shape data
Filter
T A. Lets through only the data that matches Conditions; the rest goes to false. With no condition everything passes. Outputs true, false.
Select Fields
Panel name Keep fields. T A. Keeps only the tags you list and removes the others. Setting Fields to keep.
Set Field
T A. Writes a value into a field.
| Setting | Values |
|---|---|
| Destination | The field to write. |
| Value source | Copy from field (then Source field) or Constant (then Constant value: text, number or true/false). |
A missing source field is an error.
Rename Field
T A. Settings From and To. A missing field is an error.
Remove Field
T A. Setting Field.
Convert Type
T A. Settings Field and Target type: Number (default), Integer, Boolean, String, DateTime or Any. A value that cannot be converted goes to error.
Calculate
Calculate
T A. Computes a new value from other fields.
| Setting | Values |
|---|---|
| Formula | Numbers, tag names, + - * /, brackets and the functions abs(x), round(x), min(a, b), max(a, b), clamp(value, low, high). For example flow * 60 or round(power / 1000). At most 1024 characters. |
| Output field | A new field. It must not exist yet. |
Tag names are written without payload. and must be required by the source or produced by an earlier node. Division by zero, a missing value or a result that is not a finite number goes to error. The result is a number of quality Good.
Expression
T A. The same node as Calculate, with the same settings.
Set Unit
T A. Settings Field and Unit, picked from the unit catalog (type part of a name, such as Celsius or pressure).
Set Quality
T A. Settings Field and Quality: Good, Bad or Uncertain. Later nodes that calculate refuse values that are not Good.
Add Context
T A. Adds facts about the device as attributes (attributes.site, ...). Setting Context to add: enterprise, site, area, line, equipment, device name, profile, protocol. Facts that are empty for the device are skipped.
Window and state
These nodes remember earlier values, separately for each device.
Moving Average
T A. The average of the last readings. Settings Input field, Output field, Window samples (1 to 1024, default 8).
Rate Of Change
T A. Change per second since the previous reading. Settings Input field, Output field. The first reading only starts the count and goes to error.
Event Time Window
Panel name Time window average. A. The average over a time span. Settings Input field, Output field, Duration (ms) (default 60000), Maximum samples (1 to 1024, default 128). A reading older than the window goes to error.
Latest Join
Panel name Combine. A. Puts the latest values of two devices side by side, for example inlet and outlet pressure on one line.
| Setting | Values |
|---|---|
| Pair values from | The same device, equipment, line / cell, area or site. |
| First value, Store first as | The first tag and the field it is stored in. |
| Second value, Store second as | The second tag and its field. |
| At most this far apart (ms) | Default 1000. |
| Roles (advanced) | First role, Second role: which device plays which part. |
Inputs left and right. Until both values are known and close enough in time, readings go to error.
Debounce
A. Lets through at most one reading per device in each Quiet period (ms) (default 1000). The others go to error.
Hysteresis
Panel name Band. A. Turns a value into an open or closed state with a dead band, so it does not flicker around one threshold. Settings Input field, Open at or above (default 60), Close at or below (default 40). Outputs open and closed.
Detect Anomaly
Panel name Detect unusual values. A. Compares each value with the average and spread of the recent values.
| Setting | Values |
|---|---|
| Value | The tag. |
| Learn from the last values | 10 to 1024. Default 120. |
| Sensitivity | In standard deviations, 1 to 10. Default 3. Higher means fewer findings. |
| Values before judging (warm-up) | At least 5, at most the window. |
Outputs unusual and normal. During warm-up every value is normal.
Summarize
Panel name Summarize per period. A. One result per period.
| Setting | Values |
|---|---|
| Value | The tag. |
| Summary | average, lowest value, highest value, sum of values, number of values, change of a counter, total over time (value × hours). |
| Period | 15 minutes, 30 minutes, hour, 4 hours, shift (8 hours), 12 hours, day. |
| Result field, Time zone |
Outputs period (once, when the first value of the next period arrives) and collecting (every other value). A value older than the current period is ignored.
Route
Switch
T A. Sends data to true or false. Condition type:
- Numeric comparison: Input field, Operator (
>,>=,<,<=,==,!=), Threshold. - Conditions (all / any): the same conditions as Filter.
In a pipeline that runs after data is stored, a switch can also have a lasting time: it sends data to true only once its condition has held for that long without a break, on each device. The Conditions step of the builder sets it ("once that has lasted … s"). Use it where a start-up surge or a noisy value would otherwise raise an alarm.
Split
T. Copies the data into Branches parallel branches (2 to 16). Outputs branch 1 to branch N.
Drop
Panel name Stop. T. Ends the branch; the data goes no further. Setting Operational reason.
Quarantine
T. Takes suspicious data out of normal processing so it can be inspected. Setting Operational reason. Ends the branch.
Transport Output
Panel name Continue. T. Sends the processed data on to storage and outbound targets. Ends the branch.
Alarm Status Route
Panel name Alarm status. A. Sends data to true or false depending on an alarm of this pipeline for the device. Take TRUE when the alarm is: Open, Closed (or never opened) or Open and acknowledged on the hub. Alarm: one alarm key, or any alarm of this pipeline.
Automation
Create Or Update Alarm
Panel name Open alarm. A. Opens an alarm, or updates it if it is already open. Ends the branch.
| Setting | Values |
|---|---|
| Alarm key | A short name; Clear Alarm uses the same key. |
| Severity | Info, Warning (default), Critical. |
| Message | Up to 512 characters. |
| Entity key | What the alarm is about. Default device.id. |
Clear Alarm
A. Closes an alarm opened earlier in this pipeline. Alarm to clear picks one of the pipeline's alarm keys. Ends the branch.
Notification
Panel name Notify. A. Sends Message through a Notification channel. Ends the branch. See Notification channels.
Effects
Effects reach outside Proxus. They run only when the pipeline is published in Active mode; in Shadow mode they are recorded as "would" actions. Send to target, Write to device and Call an API also need [Flows] EffectsEnabled = true on the gateway; see Configuration keys.
Target Output
Panel name Send to target. A. Sends the data to outbound targets. Ends the branch.
| Setting | Values |
|---|---|
| Targets | Current device targets, Specific outbound channel (then Outbound channel) or Platform storage only (store as tag). |
| Minimum interval (ms) | 100 or more. Default 1000. |
This is an extra delivery: the device's normal delivery to its targets continues.
Device Write
Panel name Write to device. A. Writes a value to a device's tag. Ends the branch.
| Setting | Values |
|---|---|
| Device | Ingress device (the device the data came from) or Specific device (then Fixed device). |
| Writable register | A tag that is not read-only. |
| Value field | The field holding the value. |
| Minimum, Maximum | Values outside this range are not written and go to error. |
| Minimum interval (ms) | Default 1000. |
A write is tried once, with a 10-second limit. A write that timed out is not repeated.
Call Api
Panel name Call an API. A. Fetches one value from a REST API target and stores it as a tag of a device. Ends the branch.
| Setting | Values |
|---|---|
| API connection | An outbound target of type REST API. |
| Device | The device the value is stored on. |
| Path (optional) | Added to the target's address; starts with / or ?. It cannot change the host. |
| Value in the response | Where the value is in the answer, for example data.items[0].price. |
| Store as tag | The tag name. |
Each call has a 20-second limit.
Observe
Capture Sink
Panel name Trace. T A. Keeps a short live sample of the data for the Trace tab. Setting Trace label.
Error Sink
Panel name Errors. T A. Collects and counts data that failed a step. Connect error outputs to it.
Limits of a pipeline
| Limit | Value |
|---|---|
| Nodes | 1 to 128 |
| Connections | 256 |
| Size of the definition | 256 KB |
| Sources in an automation pipeline | 8 |
| Branches from one node | 16 |
| Window size of a node | 1024 values |
| Pipelines on one gateway | 256 |
| Name | 1 to 120 characters |
The graph may not loop back, and every node must be reachable from a source. The Trace tab keeps the last 64 items per pipeline.
Related
- Pipelines: build, test and publish.
- Pipelines and rules: when to use which.
- Troubleshoot automation.